B.4 MEMORY MAPPING
Table B–9: MODBUS MEMORY MAP (Sheet 45 of 57)
ADDR
REGISTER NAME
C766
...Repeated for Control Pushbutton 4
C768
...Repeated for Control Pushbutton 5
C76A
...Repeated for Control Pushbutton 6
C76C
...Repeated for Control Pushbutton 7
Clear Records (Read/Write Setting)
B
C772
Clear Event Records operand
C773
Clear Oscillography operand
C774
Clear Data Logger operand
C77B
Clear Demand operand
C77D
Clear Energy operand
C77F
Clear Unauthorized Access operand
C781
Clear Platform Direct Input/Output Statistics operand
C782
Reserved (13 items)
Force Contact Inputs/Outputs (Read/Write Settings)
C7A0
Force Contact Input x State (96 items)
C800
Force Contact Output x State (64 items)
Direct Inputs/Outputs (Read/Write Setting)
C880
Direct Device ID
C881
Direct I/O Channel 1 Ring Configuration Function
C882
Platform Direct I/O Data Rate
C883
Direct I/O Channel 2 Ring Configuration Function
C884
Platform Direct I/O Crossover Function
Direct input/output commands (Read/Write Command)
C888
Direct input/output clear counters command
Direct inputs (Read/Write Setting) (96 modules)
C890
Direct Input 1 Device Number
C891
Direct Input 1 Number
C892
Direct Input 1 Default State
C893
Direct Input 1 Events
C894
...Repeated for Direct Input 2
C898
...Repeated for Direct Input 3
C89C
...Repeated for Direct Input 4
C8A0
...Repeated for Direct Input 5
C8A4
...Repeated for Direct Input 6
C8A8
...Repeated for Direct Input 7
C8AC
...Repeated for Direct Input 8
C8B0
...Repeated for Direct Input 9
C8B4
...Repeated for Direct Input 10
C8B8
...Repeated for Direct Input 11
C8BC
...Repeated for Direct Input 12
C8C0
...Repeated for Direct Input 13
C8C4
...Repeated for Direct Input 14
C8C8
...Repeated for Direct Input 15
C8CC
...Repeated for Direct Input 16
C8D0
...Repeated for Direct Input 17
C8D4
...Repeated for Direct Input 18
C8D8
...Repeated for Direct Input 19
C8DC
...Repeated for Direct Input 20
C8E0
...Repeated for Direct Input 21
C8E4
...Repeated for Direct Input 22
C8E8
...Repeated for Direct Input 23
C8EC
...Repeated for Direct Input 24
C8F0
...Repeated for Direct Input 25
C8F4
...Repeated for Direct Input 26
B-52
N60 Network Stability and Synchrophasor Measurement System
RANGE
UNITS
STEP
0 to 65535
---
1
0 to 65535
---
1
0 to 65535
---
1
0 to 65535
---
1
0 to 65535
---
1
0 to 65535
---
1
0 to 65535
---
1
---
---
---
0 to 2
---
1
0 to 3
---
1
1 to 16
---
1
0 to 1
---
1
64 to 128
kbps
64
0 to 1
---
1
0 to 1
---
1
0 to 1
---
1
0 to 16
---
1
0 to 96
---
1
0 to 3
---
1
0 to 1
---
1
APPENDIX B
FORMAT
DEFAULT
F300
0
F300
0
F300
0
F300
0
F300
0
F300
0
F300
0
F001
0
F144
0 (Disabled)
F131
0 (Disabled)
F001
1
F126
0 (No)
F001
64
F126
0 (No)
F102
0 (Disabled)
F126
0 (No)
F001
0
F001
0
F086
0 (Off)
F102
0 (Disabled)