5 SETTINGS
The location of the control pushbuttons are shown in the following figures.
Figure 5–5: CONTROL PUSHBUTTONS (ENHANCED FACEPLATE)
An additional four control pushbuttons are included on the standard faceplate when the N60 is ordered with the twelve
user-programmable pushbutton option.
Figure 5–6: CONTROL PUSHBUTTONS (STANDARD FACEPLATE)
Control pushbuttons are not typically used for critical operations and are not protected by the control password. However,
by supervising their output operands, the user can dynamically enable or disable control pushbuttons for security reasons.
Each control pushbutton asserts its own FlexLogic™ operand. These operands should be configured appropriately to per-
form the desired function. The operand remains asserted as long as the pushbutton is pressed and resets when the push-
button is released. A dropout delay of 100 ms is incorporated to ensure fast pushbutton manipulation will be recognized by
various features that may use control pushbuttons as inputs.
An event is logged in the event record (as per user setting) when a control pushbutton is pressed. No event is logged when
the pushbutton is released. The faceplate keys (including control keys) cannot be operated simultaneously – a given key
must be released before the next one can be pressed.
The control pushbuttons become user-programmable only if the breaker control feature is not configured for manual control
via the USER 1 through 3 pushbuttons as shown below. If configured for manual control, breaker control typically uses the
larger, optional user-programmable pushbuttons, making the control pushbuttons available for other user applications.
SETTING
CONTROL PUSHBUTTON
{
1 FUNCTION:
Enabled=1
SETTINGS
SYSTEM SETUP/
BREAKERS/BREAKER 1/
BREAKER 1 PUSHBUTTON
CONTROL
Enabled=1
SYSTEM SETUP/
BREAKERS/BREAKER 2/
BREAKER 2 PUSHBUTTON
CONTROL
Enabled=1
GE Multilin
N60 Network Stability and Synchrophasor Measurement System
Control pushbuttons
STATUS
EVENT CAUSE
IN SERVICE
VOLTAGE
TROUBLE
CURRENT
RESET
TEST MODE
FREQUENCY
TRIP
OTHER
USER 1
ALARM
PHASE A
PICKUP
PHASE B
USER 2
PHASE C
NEUTRAL/GROUND
USER 3
USER 4
USER 5
USER 6
USER 7
842733A2.CDR
:
AND
RUN
OFF
ON
:
Figure 5–7: CONTROL PUSHBUTTON LOGIC
5.2 PRODUCT SETUP
842813A1.CDR
THREE
STANDARD
CONTROL
PUSHBUTTONS
FOUR EXTRA
OPTIONAL
CONTROL
PUSHBUTTONS
TIMER
FLEXLOGIC OPERAND
0
CONTROL PUSHBTN 1 ON
100 msec
842010A2.CDR
5
5-45