GE N60 Instruction Manual page 237

Network stability and synchrophasor measurement system ur series
Hide thumbs Also See for N60:
Table of Contents

Advertisement

5 SETTINGS
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The power swing detect element provides both power swing blocking and out-of-step tripping functions. The element mea-
sures the positive-sequence apparent impedance and traces its locus with respect to either two or three user-selectable
operating characteristic boundaries. Upon detecting appropriate timing relations, the blocking and tripping indications are
given through FlexLogic™ operands. The element incorporates an adaptive disturbance detector. This function does not
trigger on power swings, but is capable of detecting faster disturbances – faults in particular – that may occur during power
swings. Operation of this dedicated disturbance detector is signaled via the
The power swing detect element asserts two outputs intended for blocking selected protection elements on power swings:
is a traditional signal that is safely asserted for the entire duration of the power swing, and
POWER SWING BLOCK
is established in the same way, but resets when an extra disturbance is detected during the power swing.
SWING UN/BLOCK
The
POWER SWING UN/BLOCK
faults during power swing conditions.
Different protection elements respond differently to power swings. If tripping is required for faults during power swing condi-
tions, some elements may be blocked permanently (using the
and dynamically unblocked upon fault detection (using the
The operating characteristic and logic figures should be viewed along with the following discussion to develop an under-
standing of the operation of the element.
The power swing detect element operates in three-step or two-step mode:
Three-step operation: The power swing blocking sequence essentially times the passage of the locus of the positive-
sequence impedance between the outer and the middle characteristic boundaries. If the locus enters the outer charac-
teristic (indicated by the
POWER SWING OUTER
cated by the
POWER SWING MIDDLE
the power swing blocking signal (
ing signal resets when the locus leaves the outer characteristic, but not sooner than the
time.
Two-step operation: If the two-step mode is selected, the sequence is identical, but it is the outer and inner character-
istics that are used to time the power swing locus.
GE Multilin
N60 Network Stability and Synchrophasor Measurement System
POWER SWING INNER
LFT BLD: 100.00 Ω
POWER SWING PICKUP
DELAY 1: 0.030 s
POWER SWING RESET
DELAY 1: 0.050 s
POWER SWING PICKUP
DELAY 2: 0.017 s
POWER SWING PICKUP
DELAY 3: 0.009 s
POWER SWING PICKUP
DELAY 4: 0.017 s
POWER SWING SEAL-IN
DELAY: 0.400 s
POWER SWING TRIP
MODE: Delayed
POWER SWING BLK:
Off
POWER SWING
TARGET: Self-Reset
POWER SWING
EVENTS: Disabled
operand may be used for blocking selected protection elements if the intent is to respond to
POWER SWING UN/BLOCK
FlexLogic™ operand) but stays outside the middle characteristic (indi-
FlexLogic™ operand) for an interval longer than
POWER SWING BLOCK
Range: 0.10 to 500.00 ohms in steps of 0.01
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: Early, Delayed
Range: Flexlogic™ operand
Range: Self-Reset, Latched, Disabled
Range: Disabled, Enabled
POWER SWING 50DD
operand), and others may be blocked
POWER SWING BLOCK
operand).
FlexLogic™ operand) is established and sealed-in. The block-
5.6 GROUPED ELEMENTS
operand.
POWER
POWER SWING PICKUP DELAY 1
POWER SWING RESET DELAY 1
5-119
5
,

Advertisement

Table of Contents
loading

Table of Contents