Name of Device Variable for CJ-
series Unit
*_SlvOutAreaCode
*_SlvOutHoldBusErr
*_SlvOutIntelMd
15 14 13 12 11 10
*_SlvOutSta
CJ-series PROFIBUS Slave Unit Operation Manual for NJ-series CPU Unit (W510)
Type
R/W
Description
USINT
R
Output area
code
BOOL
R
Data hold on
PROFIBUS fail
BOOL
R
Outputs Intel
mode
9
8
7
6
5
4
3
2
3 Data Exchange with the CPU Unit
Function
Output area code (data from Master to Slave
CPU). Indicates the area to which the unit will
write PROFIBUS output data received from its
master.
00: No assignment made
01: CIO area (CIOxxxx)
03: DM area (Dxxxxx)
04: Work area (Wxxx)
05: Holding area (Hxxx)
08: EM bank 0 (E0-xxxxx)
09: EM bank 1 (E1-xxxxx)
10: EM bank 2 (E2-xxxxx)
11: EM bank 3 (E3-xxxxx)
12: EM bank 4 (E4-xxxxx)
13: EM bank 5 (E5-xxxxx)
14: EM bank 6 (E6-xxxxx)
15: EM bank 7 (E7-xxxxx)
16: EM bank 8 (E8-xxxxx)
17: EM bank 9 (E9-xxxxx)
18: EM bank A (EA-xxxxx)
19: EM bank B (EB-xxxxx)
20: EM bank C (EC-xxxxx)
FALSE: Clear data to Host CPU
TRUE: Hold data to Host CPU
Indicates how the slave will behave on the Host
CPU I/O bus in the event the PROFIBUS data
exchange communication fails (e.g. comm.
watchdog timeout).
FALSE: Motorola (high byte first)
TRUE: Intel (low byte first)
Outputs Motorola/Intel mode
Indicates how the data bytes of a PROFIBUS
data exchange telegram are mapped to Host
CPU data words.
The values in *_SlvOutSta are provided by the
PROFIBUS master's Set_Prm telegram, and
indicated in *_SlvOutSta after both the Set_Prm
and Chk_Cfg telegrams have been accepted.
1
0
3
*_SlvOutStartAdr
3-23