Name of Device Variable for CJ-
series Unit
*_EndAdrInErr
*_StartAdrOutErr
*_EndAdrOutErr
Note When the Parameter/Configuration flag is TRUE, the status of *_FreezeSta, *_FailSafeEnblSta
and *_ParamErr are not updated.
CJ-series PROFIBUS Slave Unit Operation Manual for NJ-series CPU Unit (W510)
3 Data Exchange with the CPU Unit
Type
R/W
Description
BOOL
R
Incorrect end
address for
slave input
area
BOOL
R
Incorrect start
address for
slave output
area
BOOL
R
Incorrect end
address for
slave output
area
Function
FALSE: No error
TRUE: There is an error in the slave input area
mapping. The end address of the area as spec-
ified by the start address in the Set_Prm tele-
gram, plus the data length in the Chk_Cfg
telegram, is invalid for this CPU.
The BF indicator is BLINKING to indicate a con-
figuration or parameterisation error; no I/O data
is transferred between master and slave units.
FALSE: No error
TRUE: There is an error in the slave output
area mapping. The start address of the area as
specified in the Set_Prm telegram is invalid for
this CPU.
The BF indicator is BLINKING to indicate a con-
figuration or parameterisation error; no I/O data
is transferred between master and slave units.
FALSE: No error
TRUE: There is an error in the slave output
area mapping. The end address of the area as
specified by the start address in the Set_Prm
telegram, plus the data length in the Chk_Cfg
telegram, is invalid for this CPU.
The BF indicator is BLINKING to indicate a con-
figuration or parameterisation error; no I/O data
is transferred between master and slave units.