7 .2

Power supply check

Check that the power supply to an individual barrier circuit (or to
an MTL7798 power feed module or an MTL7799 dummy barrier
sourcing the power bus ) is functional and that the voltage across
the supply with respect to earth is correct. For example, in Figure 20
the presence of 24V on terminal 1 and 12V on terminal 2 when the
switch in the hazardous area is closed confirms the serviceability
of almost the complete circuit.
7 .3

Barrier resistance test

To test the resistance of a barrier on site, refer to figure 20 and
carry out the following procedure:
a) Unplug hazardous-area cables from terminals 3 and 4.
b) Unplug safe-area cables from terminals 1 and 2.
WARNING: Take care when handling safe-area cables; the
relay contacts in figure 20 for example could be carrying
mains voltage .
c) Measure the end-to-end resistance of the barrier by
connecting a digital multimeter (set to a suitable Ω range)
between terminals 1 and 3. The reading should typically be
slightly less (eg 1–3% lower) than the maximum end-to-end
resistance listed in tables 4 to 10 for the appropriate barrier
type or approximately 10–20% higher than the figure specified
in the safety description.
d) Check the functioning of the diode-return channel (MTL7787+,
7787P+, only) by selecting the diode test function on the
multimeter and connecting it between terminals 4 (+ve) and 2
(–ve). This measures the forward voltage drop of the Schottky
diodes in the chain: the reading should be less than 0.9V.
Repeat the test with the connections reversed (ie, terminals
4 (–ve) and 2 (+ve) for an expected reading of ∞ for the reverse
voltage drop.
e) Tests c) and d) confirm the continuity of both barrier channels.
If either channel is open-circuit it is most likely that the fuse
has blown. The safe-area circuit should be investigated in an
attempt to discover the cause of the fault.
Note: if the barrier is removed, make sure the safe-area and
hazardous-area cables disconnected during operations a) and
b) are connected to an earth-rail, a dummy barrier or insulated
completely.
c) If it is not possible to disconnect wiring to the barrier for steps
a) and b), carry out the tests given in table 4.
370Ω
3
4
MTL7787+
Plant earth via DIN-rail
Figure 20: Switch-status transfer circuit using an MTL7787 barrier
INM 7700 Rev 12
1
+24Vdc
2
12V
400Ω
30mA
12V
relay
0V
8

EQUIPMENT AND BARRIER TESTS

8 .1

Thermocouple and RTD tests

8 .1 .1
Thermocouple circuit testing
Thermocouple test and calibration equipment is rarely certified
intrinsically safe and therefore requires special authorisation before
it can be used for testing or calibrating thermocouple circuits in
hazardous areas. To overcome this problem, the thermocouple
circuits can be protected by using an MTL7760ac barrier as
shown in figure 21. This permits the thermocouple output to be
measured without needing special authorisation to use uncertified
thermocouple test equipment.
As it is seldom possible to measure accurately the temperatures of
thermocouples located in hazardous areas, a safe way of adjusting
calibration tables to compensate for plant temperatures is needed.
This can be done by disconnecting the compensating cables from
the thermocouple, shorting them together, and measuring the
temperature of the shorting point.
8 .1 .2
Resistance temperature detector (RTD) circuit
testing
Resistance temperature detector (RTD) circuits can be tested
by disconnecting the measuring leads from the RTD head in
the hazardous area and connecting them to a resistance box.
Sometimes it is more convenient to connect the resistance box in
the safe area, for instance at point 'xx' in figure 22. For the latter
method, however, the RTD must be shorted out or an allowance
made for its temperature. The effect of a negative temperature
change can be simulated by connecting the resistance box into the
measurement lead at point 'yy'. The advantage of connecting the
resistance box at the RTD head is that any leakage can also be
determined by connecting the resistance box at point 'yy'.
8 .2

Barrier tests

8 .2 .1
General
MTL7700 range of barriers do not need to be subjected to routine
testing if they are in normal use. Generally, the inspection tests
described in section 6 are more than adequate. However, if the
performance of barriers is in any way suspect, then carry out the
detailed tests described in this section. Barriers which pass these
tests satisfactorily are highly unlikely to represent an unacceptable
level of risk or cause a circuit malfunction.
There are two types of test (as shown by tables 4 to 10); a simple
test using a digital multimeter to test barriers on site and a more
comprehensive bench test using a constant current source to
establish the breakdown characteristics.
Although certification requirements concentrate on pulse-
current tests, in many ways the leakage current tests described
in this section are a more satisfactory method of testing suspect
diodes. If a complete functional check of a barrier is needed, then
the multimeter and constant current tests described in sections
8.2.2 and 8.2.3 should be made although, for most purposes, the
multimeter tests should suffice.
Compensating cables
3
3
4
4
Figure 21: Calibrating a thermocouple barrier circuit
11
Safe-area
equipment
1
1
2
2
MTL7760ac