QUBINO Flush 2 relay User Manual page 47

Z-wave
Table of Contents

Advertisement

Parameter no. 30 - Restore on/off status for Q1 and Q2 loads after power failure
This parameter determines if on/off status is saved and restored for both loads after power
failure.
Values (size is 1 byte dec):
• default value 0
• 0 - Device saves last on/off status and restores it after a power failure
• 1 - Device does not save on/off status and does not restore it after a power failure, it
remains off.
Parameter no. 40 – Watt Power Consumption Reporting Threshold for Q1 Load
Choose by how much power consumption needs to increase or decrease to be reported. Values
correspond to percentages so if 10 is set (by default), the device will report any power
consumption changes of 10% or more compared to the last reading.
Values (size is 1 byte dec):
• default value 50
• 0 - Power consumption reporting disabled
• 1 - 100 = 1% - 100% Power consumption reporting enabled. New value is reported only
when Wattage in real time changes by more than the percentage value set in this
parameter compared to the previous Wattage reading, starting at 1% (the lowest value
possible).
NOTE: Power consumption needs to increase or decrease by at least 1 Watt to be reported,
REGARDLESS of percentage set in this parameter.
47
EN.