Download Print this page

Uponor Smatrix Move PLUS Quick Manual page 13

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 4
N O T E !
Some system parameter settings are only
accessible during the fi rst 4 hours after
power up. This is done to prevent mistakes
after installation. If the locked system
parameter symbol
is displayed, the power
to the controller has to be disconnected
and reconnected again to modify these
parameters. No settings are lost when
disconnecting or after a power failure.
The settings available while in run mode is
always accessible for change, and will not be
locked.
To enter system parameter settings:
1. Press and hold the OK button for about 10 seconds.
2. The settings icon is displayed in the top left hand
corner of the display, and the text Hot type, Cld
type, or rEv type (depending of current operating
mode) is displayed.
3. Use buttons < or > to locate a parameter (see list
below) and press OK.
Some of these parameters require other parameters
to activate them.
Menu
Display
Description
0
type
Type of installation (heating and/
or cooling)
1
Cur
Heating curve
See page 12 for more information
and a diagram
2
Hi
Maximum supply temperature
(heating mode)
3
Lo
Minimum supply temperature
(heating mode)
Cur
1
Cooling curve
See page 12 for more information
and a diagram
2
Hi
Maximum supply temperature
(cooling mode)
3
Lo
Minimum supply temperature
(cooling mode)
InSt
4
Type of system (hydraulic
installation)
5
th
Thermostat selection (installed/
wireless/etc, see the registration
instruction on pages 8 – 10)
U P O N O R S M AT R I X M O V E P L U S · Q U I C K G U I D E
Q U I C K G U I D E
Menu
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
4. Use buttons - or + to change parameter settings.
5. Use buttons < or > to locate parameter 24 (End)
– Exit system parameter settings.
6. Press the OK button to exit the system parameter
settings.
Display
Description
tHty
Not used by Move PLUS
BGAP
Not used by Move PLUS
trF1
Wireless thermostat 1 confi guration
(see the registration instruction on
pages 8 – 10)
trF2
Wireless thermostat 2 confi guration
(see the registration instruction on
pages 8 – 10)
This thermostat controls the
operation of circulation pump 2
tr1o
Supply temperature compensation
when using a thermostat to speed
up the system. Use with caution
in1
Wired input 1, select function
in2
Wired input 2, select function
OUSE
Outdoor sensor selection
(installed/wireless/wired/etc,
see the registration instruction on
pages 8 – 10)
OUt
Outdoor temperature, fi xed value if
outdoor sensor is not installed
ourF
Wireless outdoor sensor
confi guration (see the registration
instruction on pages 8 – 10)
˚C
Display unit
00:00
Time unit (AM/PM/24H)
GriP
Valve and pump exercise
PUMP
Pump start delay after the mixer
valve is closed
ctrl
Forced control of the actuator
PrH
Floor/screed preheating program
DIN 1264-4
dry
Floor/screed drying program
ALL
Factory reset
Press and hold the OK button for
about 5 seconds
End
Exit system parameter settings
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
1 3

Advertisement

loading