Toshiba P9 Installation & Operation Manual page 98

Adjustable speed drive asd
Hide thumbs Also See for P9:
Table of Contents

Advertisement

F106
Input Terminal Priority
Program Terminal Input Special Functions
This parameter is used to allow the Jog and DC Injection Braking input
signals to control the ASD when received via the Terminal Board even though
the system is in the Hand mode.
With this parameter enabled, a Jog command or a DC Injection Braking
command received from the Terminal Board will receive priority over
commands from the EOI.
See
F260
for additional information on using the Jog function.
See
F250
F252
for additional information on DC Injection Braking.
Settings:
0 — Disabled
1 — Enabled
16-Bit Binary/BCD Input
Program Terminal Input Special Functions
The extended terminal function is used with the Expansion IO Card Option
(P/N ETB004Z).
This parameter defines the format of the binary or BCD data when using the
option card.
Note:
The Expansion IO Card Option 2 option board is required to
use this terminal.
See the Expansion IO Card Option 1 Instruction Manual (P/N 58685) for
additional information on the function of this terminal.
Settings:
0 — None
1 — 12-Bit Binary
2 — 16-Bit Binary
3 — 3-Digit BCD
4 — 4-Digit BCD
5 — Inverted 12-Bit Binary
6 — Inverted 16-Bit Binary
7 — Inverted 3-Digit BCD
8 — Inverted 4-Digit BCD
Selections using 16-bit binary or 4-digit BCD will require the configuration of
terminals S1-S4 on the Terminal Board as binary bits 0 – 3
Frequency Mode 1 (F004) parameter must be set to Binary/BCD.
For proper scaling of the binary or BCD input, parameters
configured.
88
Direct Access Number — F106
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — No
Direct Access Number — F107
Parameter Type — Selection List
Factory Default — None
Changeable During Run — No
(F115 –
F118). The
F228
F231
must be
P9 ASD Installation and Operation Manual
F107

Advertisement