Toshiba P9 Installation & Operation Manual page 221

Adjustable speed drive asd
Hide thumbs Also See for P9:
Table of Contents

Advertisement

F721
Panel Stop Pattern
Program Special Operation Panel Parameters
While operating in the Hand mode, this parameter determines the method used
to stop the motor when the stop command is issued via the EOI.
The Deceleration Stop selection enables the Dynamic Braking system that is
set up at
F304
or the DC Injection Braking system that is set up at F250, F251,
and F252.
The Coast Stop setting allows the motor to stop at the rate allowed by the
inertia of the load.
Settings:
0 — Deceleration Stop
1 — Coast Stop
Note:
The Stop Pattern setting has no effect on the Emergency Off
settings of F603. This parameter may also be accessed by
pressing the ESC key from the Frequency Command screen.
Panel Torque Command
Program Special Operation Panel Parameters
This function is not used with the P9 ASD.
The Torque Command selection is performed at F420.
Panel Tension Torque Bias
Program Special Operation Panel Parameters
This function is not used with the P9 ASD.
The Tension Torque Bias selection is performed at F423.
Panel Load Sharing Gain
Program Special Operation Panel Parameters
This function is not used with the P9 ASD.
The Load Sharing Gain selection is performed at F424.
Panel Override Multiplication Gain
Program Special Operation Panel Parameters
This parameter provides a value to be used in the event that Setting (F729) is
selected for the Frequency Override Multiplying Input (F661).
P9 ASD Installation and Operation Manual
Direct Access Number — F721
Parameter Type — Selection List
Factory Default — Deceleration Stop
Changeable During Run — Yes
Direct Access Number — F725
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — -250.00
Maximum — +250.00
Direct Access Number — F727
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — -250.00
Maximum — +250.00
Units — %
Direct Access Number — F728
Parameter Type — Numerical
Factory Default — 100.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.00
Units — %
Direct Access Number — F729
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — -100.00
Maximum — 100.00
Units — %
F729
211

Advertisement

Table of Contents
loading

Table of Contents