Table 6. Discrete Input Terminal Assignment Selections and Descriptions. (Continued)
*Sel. No.
NO NC
Low Suction/No Flow Protection — Will not allow the ASD to start if activated, or terminates the ASD output
138 139
upon activation (if running) in the event of the loss of feed water or a closed output valve at the pump output.
Sealing Water — Once an adequate water supply is detected at the pump seal via a reed switch, activation enables
140 141
the ASD for normal operations.
Virtual Linear Pump Enable/Disable — Activation enables the Virtual Linear Pump function for normal
142 143
operation. The Virtual Linear Pump function is disabled when the terminal is not active.
144 145 ON Float — Activation runs the ASD at the setting of F456.
OFF Float — Activation has a dual function:
146 147
1) Changes the operating mode from Process Hold to Direct.
2) Turns off the ASD.
148 149 Trigger Float — Activation changes the operating mode from Process Hold to Direct.
Alarm Float — This input is typically connected to a float switch that, when activated, annunciates that the fluid level
150 151
is now critical. The discrete output terminals OUT1 and/or OUT2 may be associated with the activation (set OUT1/
OUT2 to TBA Alarm Float to activate an auxiliary system — i.e., aux pump, relief valve, audible/visual alarm, etc.).
TBA HOA Switch — Activation enables Time-Based Alternation operation. Operates in conjunction with the
152 153
setting of F417.
NO/NC = Normally Open/Normally Closed.
*Selection numbers are used when configuring the ASD via communications. The Normally Open (NO) or Normally
Closed (NC) configuration must be chosen by selecting the associated number.
248
Terminal Selection Descriptions
P9 ASD Installation and Operation Manual