Toshiba P9 Installation & Operation Manual page 137

Adjustable speed drive asd
Hide thumbs Also See for P9:
Table of Contents

Advertisement

F260
Jog Run Frequency
Program Frequency Jog Settings
This parameter sets the output frequency of the ASD during a Jog. Jogging is
the term used to describe turning on the motor for small increments of time and
is used when precise positioning of motor-driven equipment is required.
The Jog function is initiated via the Terminal Board or using
Communications (see the 7-Series Serial Communications User Manual
(P/N 53840) for additional information on using Communications for
Jogging).
To perform a Jog, set this parameter (F260) to the desired Jog frequency.
Select a Jog Stop method (F261).
Jog Run Using the Terminal Board
To initiate a Jog from the Terminal Board, perform the following:
1.
Assign an unused discrete input terminal to the Jog setting.
2.
Assign a discrete input terminal to the F (Forward) function (and Reverse if
required) (see
Table 6 on pg.
3.
Provide a Forward (and/or Reverse) command from the Terminal Board.
4.
Place the system in the Auto mode (Hand/Auto LED is off).
5.
Activate the Jog terminal of
The system will run at the
F260
and will stop using the
F261
Jog Stop Pattern
Program Frequency Jog Settings
This parameter sets the stopping method used while operating in the Jog mode.
Note:
This parameter setting is used for the Jog operation only. The
Emergency Off stopping method setting of
over this setting, and changes made here do not affect the
function or setting of F603.
Settings:
0 — Deceleration Stop
1 — Coast Stop
2 — DC Injection Braking Stop
P9 ASD Installation and Operation Manual
245).
Step
1.
speed for the duration of the terminal activation
method upon terminal deactivation.
F603
Direct Access Number — F260
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.0
Maximum — 20.0
Units — Hz
Direct Access Number — F261
Parameter Type — Selection List
Factory Default — Deceleration Stop
Changeable During Run — Yes
has priority
F261
127