Gas Piping - York PCG6B42 Installation Manual

Pcg6 series single package air conditioner / gas heat 3 thru 5 tons -208/230v - 3 phase
Hide thumbs Also See for PCG6B42:
Table of Contents

Advertisement

Table 6: Physical Data (Continued)
NOMINAL TONNAGE:
Direct Drive Indoor Fan Data
Fan Size (Inch)
Type
Motor HP each
RPM
Frame size
Filters
Filter Size
Quantity - Size
COMPRESSORS
CAUTION
!
This system uses R-410A refrigerant which operates at higher pres-
sures than R-22. No other refrigerant may be used in this system.
The compressor used in this product is specifically designed to operate
with R-410A refrigerant and cannot be interchanged. Compressors
used in PCG6 models contain two internal bypass ports which enable
the compressor to operate at 67% part load capacity.
CAUTION
!
Scroll compressors require proper rotation to operate properly. Fail-
ure to check and correct rotation may result in property damage.
NOTICE
Three-phase, scroll compressors operate in only one direction. If the
scroll is drawing low amperage, has similar suction and discharge
pressures, or is producing a high noise level, the scroll is misphased.
Check compressor rotation. If the scroll is misphased, change the
incoming line connection phasing to obtain the proper rotation.
The compressor uses polyolester (POE oil), Mobile 3MA POE. This oil
is extremely hydroscopic, meaning it absorbs water readily. POE oil can
absorb 15 times as much water as other oils designed for HCFC and
CFC refrigerants. If refrigerant circuit is opened, take all necessary pre-
cautions to avoid exposure of the oil to the atmosphere.
CAUTION
!
Do not leave the system open to the atmosphere. Unit damage could
occur due to moisture being absorbed by the POE oil in the system.
This type of oil is highly susceptible to moisture absorption
POE (polyolester) compressor lubricants are known to cause long term
damage to some synthetic roofing materials.
Johnson Controls Unitary Products
MODELS:
PCG6B36
3.0
11 x 10
Centrifugal
1/2
3/4
1200 Max
48
B
Field-supplied external filters must be sized so as not to exceed 300 fpm air velocity through dis-
posable filters. For internal filter use, a filter rack kit is available. Consult the instructions supplied
with that kit for replacement filter sizes. Filter sizes: A=20x20, B=20x30.
PCG6B42
PCG6B48
3.5
4.0
11 x 10
11 x 10
Centrifugal
Centrifugal
3/4
3/4
1200 Max
1200 Max
48
48
B
B
CAUTION
!
Exposure, even if immediately cleaned up, may cause embrittlement
(leading to cracking) to occur in one year or more. When performing
any service that may risk exposure of compressor oil to the roof, take
precautions to protect roofing.
Procedures which risk oil leakage include, but are not limited to, com-
pressor replacement, repairing refrigerant leaks, replacing refrigerant
components such as filter drier, pressure switch, metering device or
coil.
CAUTION
!
Do not loosen compressor mounting bolts.
Units are shipped with compressor mountings which are factory-
adjusted and ready for operation.
GAS HEAT
These two stage gas-fired heat sections have direct spark ignition.

GAS PIPING

Proper sizing of gas piping depends on the cubic feet per hour of gas
flow required, specific gravity of the gas and the length of run. National
Fuel Gas Code Z223.1 or CSA B149.1 should be followed in all cases
unless superseded by local codes or gas company requirements. Refer
to Tables 7 and 8.
The BTU content of the gas may differ with locality. The value should be
checked with the local gas utility.
NOTICE
There may be a local gas utility requirement specifying a minimum
diameter for gas piping. All units require a 1/2 inch pipe connection at
the gas valve.
5285473-UIM-E-1217
PCG6B60
5.0
11 x 10
Centrifugal
1
1200 Max
48
B
9