Unit Limitations - York PCG6B42 Installation Manual

Pcg6 series single package air conditioner / gas heat 3 thru 5 tons -208/230v - 3 phase
Hide thumbs Also See for PCG6B42:
Table of Contents

Advertisement

LIMITATIONS
These units must be installed in accordance with the following:
In U.S.A.:
1. National Electrical Code, ANSI/NFPA No. 70 - Latest Edition
2. National Fuel Gas Code, ANSI Z223.1 - Latest Edition
3. Gas-Fired Central Furnace Standard, ANSI Z21.47a. - Latest Edi-
tion
4. Local building codes
5. Local gas utility requirements
In Canada:
1. Canadian Electrical Code, CSA C22.1
2. Installation Codes, CSA - B149.1.
3. Local plumbing and waste water codes
4. Other applicable local codes.
Table 1: Unit Limitations
Model
All Models
FIGURE 1: Component Location
LOCATION
WARNING
!
Excessive exposure of this unit to contaminated combustion air may
result in equipment damage or personal injury. Typical contaminates
include: permanent wave solution, chlorinated waxes and cleaners,
chlorine based swimming pool chemicals, water softening chemicals,
carbon tetrachloride, Halogen type refrigerants, cleaning solvents
(e.g. perchloroethylene), printing inks, paint removers, varnishes,
hydrochloric acid, cements and glues, anti-static fabric softeners for
clothes dryers, masonry acid washing materials.
Use the following guidelines to select a suitable location for these units:
Johnson Controls Unitary Products
Unit Voltage
208/230-3-60
Refer to unit application data found in this document.
After installation, gas fired units must be adjusted to obtain a temperature
rise within the range specified on the unit rating plate.
If components are to be added to a unit to meet local codes, they are to
be installed at the dealer's and/or customer's expense.
Size of unit for proposed installation should be based on heat loss/heat
gain calculation made according to the methods of Air Conditioning
Contractors of America (ACCA).
This furnace is not to be used for temporary heating of buildings or
structures under construction.

Unit Limitations

Applied Voltage
Min
Max
187
252
WARNING
!
Do not attach supply and return duct work to the bottom of the unit
base pan as the drain pan could be compromised.
outdoor installation
1. Unit is designed for
2. Condenser coils must have an unlimited supply of air. Where a
choice of location is possible, position the unit on either north or
east side of building.
3. Suitable for mounting on roof curb.
4. For ground level installation, a level pad or slab should be used.
The thickness and size of the pad or slab used should meet local
codes and requirements of unit weight. Do not tie the slab to the
building foundation.
5285473-UIM-E-1217
Outdoor DB Temp
Max (°F)
125
only.