York PCE4 Series Installation Manual

York PCE4 Series Installation Manual

Single package air conditioner/electric

Advertisement

INSTALLATION MANUAL

SINGLE PACKAGE
AIR CONDITIONER/ELECTRIC
MODELS: PCE4 Series
(2-5 Ton)
GENERAL INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
MODEL NUMBER NOMENCLATURE . . . . . . . . . . . . . . . . . . . . . . . 2
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
AIRFLOW PERFORMANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Component Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Unit 4 Point Load Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Bottom Duct Dimensions (inches) . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Rear Duct Dimensions (inches) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Typical Field Power Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . 7
Unit Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Weights and Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Unit Clearances, . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Single Point Connection Kit Required . . . . . . . . . . . . . . . . . . . . . . . . 8
Electrical Data for 208-1-60 Multi Source Power . . . . . . . . . . . . . . . . 9
Electrical Data for 230-1-60 Multi Source Power . . . . . . . . . . . . . . . 10
SECTION I: GENERAL INFORMATION
PCE units are factory assembled air conditioners designed for outdoor
installation on a roof top or a slab. Field-installed electric heater acces-
sories are available to provide electric heat.
The units are completely assembled on rigid, removable base rails. All
piping, refrigerant charge, and electrical wiring is factory installed and
tested. The units require only electric power and duct connections at
the point of installation.
SECTION II: SAFETY
This is a safety alert symbol. When you see this symbol on
labels or in manuals, be alert to the potential for personal
injury.
Understand and pay particular attention to the signal words DANGER,
WARNING, or CAUTION.
DANGER indicates an imminently hazardous situation, which, if not
avoided, will result in death or serious injury.
WARNING indicates a potentially hazardous situation, which, if not
avoided, could result in death or serious injury.
Johnson Controls Unitary Products
LIST OF SECTIONS
OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
TYPICAL WIRING DIAGRAMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
START UP SHEET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
LIST OF FIGURES
Single Point Wiring Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Measuring External Static Pressure . . . . . . . . . . . . . . . . . . . . . . . . . 17
Connection Wiring Diagram - 2 to 3 Ton Models . . . . . . . . . . . . . . . 18
Ladder Wiring Diagram - 2 to 3 Ton Models . . . . . . . . . . . . . . . . . . . 19
Ladder Wiring Diagram - 3.5 to 5 Ton Models . . . . . . . . . . . . . . . . . 21
R-410A Quick Reference Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
LIST OF TABLES
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Airflow - Side Duct Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Airflow - Bottom Duct Application . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Electric Heat Minimum Supply Air . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Electric Heat Multipliers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Additional Static Resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Thermostat Signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
CAUTION indicates a potentially hazardous situation, which, if not
avoided may result in minor or moderate injury. It is also used to
alert against unsafe practices and hazards involving only property dam-
age.
Improper installation may create a condition where the operation of
the product could cause personal injury or property damage.
Improper installation, adjustment, alteration, service or maintenance
can cause injury or property damage. Failure to carefully read and
follow all instructions in this manual can result in furnace mal-
function, death, personal injury and/or property damage. Only a
qualified contractor, installer or service agency should install this
product.
This product must be installed in strict compliance with the installa-
tion instructions and any applicable local, state, and national codes
including, but not limited to building, electrical, and mechanical
codes.
® ®
WARNING
!
CAUTION
!
5126744-UIM-D-1015

Advertisement

Table of Contents
loading

Summary of Contents for York PCE4 Series

  • Page 1: Table Of Contents

    SINGLE PACKAGE ® ® AIR CONDITIONER/ELECTRIC MODELS: PCE4 Series (2-5 Ton) LIST OF SECTIONS GENERAL INFORMATION ....... . 1 OPERATION .
  • Page 2: Model Number Nomenclature

    5126744-UIM-D-1015 Due to system pressure, moving parts, and electrical components, WARNING installation and servicing of air conditioning equipment can be hazard- ous. Only qualified, licensed service personnel should install, repair, or Before performing service or maintenance operations on unit, turn off service this equipment.
  • Page 3: Component Location

    5126744-UIM-D-1015 OUTDOOR FAN MOTOR OUTDOOR FAN OUTDOOR COIL COIL GUARD PANEL (Behind Panel) CONTACTOR CAPACITOR TRANSFORMER COMPRESSOR BLOWER MOTOR OPTIONAL ELECTRIC HEAT KIT INDOOR COIL INDOOR BLOWER REMOVABLE BASE RAILS A0411-001 FIGURE 1: Component Location Table 1: Unit Limitations Unit Limitations Model Unit Voltage Applied Voltage...
  • Page 4: Unit 4 Point Load Weight

    5126744-UIM-D-1015 LOCATION CAUTION Use the following guidelines to select a suitable location for these units: outdoor installation 1. Unit is designed for only. Before lifting, make sure the unit weight is distributed equally on the 2. Outdoor coils must have an unlimited supply of air. Where a choice rigging cables so it will lift evenly.
  • Page 5: Unit Dimensions

    5126744-UIM-D-1015 COIL GUARD HIGH VOLTAGE CONNECTION 7/8” HIGH VOLTAGE CONNECTION 1-3/32” HEAT SECTION COMPRESSOR ACCESS PANEL ACCESS PANEL CONDENSATE DRAIN BLOWER ACCESS LOW VOLTAGE CONNECTION CONTROL ACCESS PANEL PANEL A0379-001 FIGURE 3: Unit Dimensions Table 3: Unit Dimensions Dimensions Model 51-1/4 35-3/4 51-1/4...
  • Page 6: Bottom Duct Dimensions (Inches)

    5126744-UIM-D-1015 1. Remove the duct covers found in the bottom return and supply air duct openings. There are four (4) screws securing each duct cover (save these screws to use in Step 2). 2. Install the duct covers (removed in step one) to the rear supply and return air duct openings.
  • Page 7: Typical Field Control Wiring Diagram For Air Conditioner Models

    5126744-UIM-D-1015 Unit comes wired for 230 volt power. If supply power is 208 volt, wires CAUTION connected to the control transformer 230V tap must be moved to the 208V tap. This system uses R-410A Refrigerant which operates at higher pres- sures than R-22.
  • Page 8: Electrical Data - 208/230-1-60 - Single Source Power

    5126744-UIM-D-1015 Table 5: Electrical Data - 208/230-1-60 - Single Source Power Single Point Connection Kit Required Electric Heat Option OD Fan Blower Max Fuse Compressor Motor Motor Model Heater kW Heater Amps (Amps) Breaker Size Heater Kit Stages LRA MCC none 16.0 16.0...
  • Page 9: Electrical Data For 208-1-60 Multi Source Power

    5126744-UIM-D-1015 Table 6: Electrical Data for 208-1-60 Multi Source Power Electric Heat Option OD Fan Blower Compressor Multi Source Motor Motor Model Heater kW Heater Amps Heater Kit Stages RLA LRA MCC Circuit #1 Compressor Circuit Circuit #2 Heat Multi Source: Compressor Multi Source: Circuit and Heat Circuits Amps...
  • Page 10: Electrical Data For 230-1-60 Multi Source Power

    5126744-UIM-D-1015 Table 6: Electrical Data for 208-1-60 Multi Source Power (Continued) Electric Heat Option OD Fan Blower Compressor Multi Source Motor Motor Model Heater kW Heater Amps Heater Kit Stages RLA LRA MCC Circuit #1 Compressor Circuit Circuit #2 Heat Multi Source: Compressor Multi Source: Circuit and Heat Circuits...
  • Page 11: Johnson Controls Unitary Products

    5126744-UIM-D-1015 Table 7: Electrical Data for 230-1-60 Multi Source Power Electric Heat Option OD Fan Blower Compressor Multi Source Motor Motor Model Heater kW Heater Amps Heater Kit Stages RLA LRA MCC Circuit #1 Compressor Circuit Circuit #2 Heat Multi Source: Compressor Multi Source: Circuit and Heat Circuits Amps...
  • Page 12: Single Point Wiring Kits

    5126744-UIM-D-1015 Single Point Kit P/N Unit Model Number Breaker Size Heat Kit S1-2SPWK008 PCE4A24 20 Amp up to 13 kW S1-2SPWK006 PCE4A30 25 Amp up to 15 kW S1-2SPWK001 PCE4A36 30 Amp up to 15 kW S1-2SPWK006 PHE4A24 25 Amp up to 13 kW S1-2SPWK002 PHE4A30...
  • Page 13: Physical Data

    5126744-UIM-D-1015 Table 8: Physical Data MODELS NOMINAL TONNAGE AHRI Cooling Performance Gross Capacity @ AHRI A point (MBH) 23.7 30.1 37.2 43.5 47.7 55.0 AHRI net capacity (MBH) 22.8 29.0 34.6 40.7 45.5 52.5 11.0 11.0 11.0 11.0 11.0 11.0 SEER 14.0 14.0...
  • Page 14: Airflow Performance

    5126744-UIM-D-1015 COMPRESSORS POE (polyolester) compressor lubricants are known to cause long term damage to some synthetic roofing materials. The compressor used in this product is specifically designed to operate CAUTION with R-410A Refrigerant and cannot be interchanged. CAUTION Exposure, even if immediately cleaned up, may cause embrittlement (leading to cracking) to occur in one year or more.
  • Page 15: Airflow - Bottom Duct Application

    5126744-UIM-D-1015 Table 10: Airflow - Bottom Duct Application External Static Pressure (Inches WC) Model Motor Speed SCFM SCFM SCFM SCFM SCFM SCFM SCFM SCFM Low (1) Low/Medium (2) 1033 Medium (3) 1186 1133 1095 1056 1016 Medium/High (4) 1357 1322 1284 1248 1211...
  • Page 16: Operation

    5126744-UIM-D-1015 SECTION VI: OPERATION Table 13: Additional Static Resistance The following sequences of operation are based on using a single- Size (Tons) Wet Indoor Coil Economizer Filter/Frame Kit stage air conditioning thermostat. 0.01 0.00 0.01 COOLING SEQUENCE OF OPERATION 0.01 0.00 0.02 0.01...
  • Page 17: Maintenance

    5126744-UIM-D-1015 STARTUP 8. Make sure all units panels are in place and secured, and that an air filter is installed. 1. Check the electrical supply voltage being supplied. Be sure that it is EXTERNAL STATIC PRESSURE SETUP within the specified range on the unit data plate. 2.
  • Page 18: Typical Wiring Diagrams

    5126744-UIM-D-1015 SECTION VIII: TYPICAL WIRING DIAGRAMS CONNECTION WIRING DIAGRAM COOLING UNIT WITH OR WITHOUT ELECTRIC HEAT WITH RECIPROCATING COMPRESSOR 208/230-1-60 CAUTION - OPEN ALL DISCONNECTS POWER SUPPLY BEFORE SERVICING THIS UNIT 208/230-1-60 OPTIONAL CRANKCASE HEATER USE COPPER CONDUCTORS CRANKCASE TEMPERATURE HEATER SWITCH ONLY...
  • Page 19: Ladder Wiring Diagram - 2 To 3 Ton Models

    5126744-UIM-D-1015 LADDER WIRING DIAGRAM COOLING UNIT WITH OR WITHOUT ELECTRIC HEAT WITH RECIPROCATING COMPRESSOR 208/230-1-60 OPTIONAL CRANKCASE HEATER WIRING CAUTION - OPEN ALL DISCONNECTS GROUND CRANKCASE TEMPERATURE BEFORE SERVICING THIS UNIT HEATER SWITCH NOTES: 1. ALL FIELD WIRING TO BE ACCOMPLISHED FOLLOWING CITY, LOCAL AND/OR NATIONAL CODES IN EFFECT AT THE TIME OF INSTALLATION COMPRES OF THE UNIT.
  • Page 20: Connection Wiring Diagram - 3.5 To 5 Ton Models

    5126744-UIM-D-1015 CONNECTION WIRING DIAGRAM COOLING UNIT WITH OR WITHOUT ELECTRIC HEAT WITH SCROLL COMPRESSOR 208/230-1-60 POWER SUPPLY 208/230-1-60 USE COPPER CAUTION - OPEN ALL DISCONNECTS CONDUCTORS OPTIONAL CRANKCASE HEATER ONLY CRANKCASE TEMPERATURE BEFORE SERVICING THIS UNIT HEATER SWITCH BLK 6 208V PUR 1 230V...
  • Page 21: Ladder Wiring Diagram - 3.5 To 5 Ton Models

    5126744-UIM-D-1015 LADDER WIRING DIAGRAM COOLING UNIT WITH OR WITHOUT ELECTRIC HEAT WITH SCROLL COMPRESSOR 208/230-1-60 CAUTION - OPEN ALL DISCONNECTS BEFORE SERVICING THIS UNIT LINE VOLTAGE OPTIONAL CRANKCASE HEATER WIRING GROUND FIELD INSTALLED POWER CRANKCASE TEMPERATURE HEATER SWITCH LOW VOLTAGE FIELD INSTALLED CONTROL NOTES: COMPRES...
  • Page 22: R-410A Quick Reference Guide

    5126744-UIM-D-1015 R-410A QUICK REFERENCE GUIDE Refer to Installation Instructions for specific installation requirements R-410A refrigerant operates at 50 - 70 percent higher pressures than R-22. Be sure that servicing equipment and replacement components are designed to operate with R-410A. R-410A refrigerant cylinders are rose colored. Recovery cylinder service pressure rating must be 400 psig, DOT 4BA400, or DOT BW400.
  • Page 23: Start Up Sheet

    5126744-UIM-D-1015 SECTION IX: START UP SHEET Residential Package Unit Cooling With Electric Heat Start-Up Sheet Print Form Reset Form Proper start-up is critical to customer comfort and equipment longevity Start-Up Date Company Name Start-Up Technician Owner Information Name Address Daytime Phone City State or Province Zip or Postal Code...
  • Page 24: Electric Heat

    Explain the importance of regular filter replacement and equipment maintenance Comments and Additional Job Details Subject to change without notice. Published in U.S.A. 5126744-UIM-D-1015 Copyright © 2015 by Johnson Controls, Inc. All rights reserved. Supersedes: 5126744-UIM-C-0715 York International Corp. 5005 York Drive Norman, OK 73069...

Table of Contents