OPTIONAL ELECTRIC HEAT

The factory-installed heaters are wired for single point power
supply. Power supply need only be brought into the single
point terminal block.
These CSA approved heaters are located within the central
compartment of the unit with the heater elements extending
in to the supply air chamber.
Fuses are supplied, where required, by the factory. Some kW
sizes require fuses and others do not. refer to Table 31 for
minimum CFM limitations and to Tables 9 through 28 for elec-
trical data.
TABLE 31: MINIMUM SUPPLY AIR CFM
Heater
Unit Model Size (Nominal Tons)
-06 (6.5) -07 (7.5) -08 (8.5) -10 (10) -12 (12.5)
kW
Voltage
9
1950
18
1950
208/
24
1950
230
36
1950
54
-
9
1950
18
1950
24
480
1950
36
1950
54
-
9
1950
18
1950
24
600
1950
36
1950
54
-

OPTIONAL GAS HEAT

These gas-fired heaters have aluminized-steel or optional
stainless steel, tubular heat exchangers with spark ignition.
TABLE 32: GAS APPLICATION DATA
Unit
Input (MBH) Output (MBH)
Size
Opt.
10
120
-06
15
180
10
120
-07
15
180
10
120
-08
15
180
15
180
-10
20
240
15
180
-12
20
240
Unitary Products Group

Minimum Supply Air CFM

2250
2550
-
2250
2550
3000
2250
2550
3000
2250
2550
3000
-
-
3000
2250
2550
-
2250
2550
3000
2250
2550
3000
2250
2550
3000
-
-
3000
2250
2550
-
2250
2550
3000
2250
2550
3000
2250
2550
3000
-
-
3000
Temp Rise
96
20-50
144
35-65
96
15-45
144
30-60
96
15-45
144
30-60
144
20-50
192
30-60
144
10-40
192
20-50

GAS PIPING

Proper sizing of gas piping depends on the cubic feet per
hour of gas flow required, specific gravity of the gas and the
length of run. "National Fuel Gas Code" Z223.1 (in U.S.A.) or
the current Gas Installation Codes CSA-B149.1 (in Canada)
should be followed in all cases unless superseded by local
codes or gas utility requirements. Refer to the Pipe Sizing
Table 33. The heating value of the gas may differ with locality.
The value should be checked with the local gas utility.
NOTE: There may be a local gas utility requirement specify-
ing a minimum diameter for gas piping. All units
require a one-inch pipe connection at the entrance
fitting.
-
3750
3750
3750
3750
-
3750
3750
3750
3750
-
3750
3750
3750
FIGURE 21 - SIDE ENTRY GAS PIPING
3750
(°F)
FIGURE 22 - BOTTOM ENTRY GAS PIPING
O P T I O N A L
C O I L
G U A R D
S H O W N
OPTIONAL
COIL
GUARD
SHOWN