1. Heating capacity valid for elevations up to 2000 feet above sea level. For elevations above 2,000 feet, rated capacity should be reduced by 4% for each 1,000 feet
above sea level.
2. Based on 1075 BTU Per Cu. Ft.
1,4
Table 10: Propane
(LP) Gas Application Data
Available On Models
3, 3-1/2, 4, 5 Tons
3, 3-1/2, 4, 5 Tons
4, 5 Tons
NOTES:
1.
Propane applications are accomplished by field installation of a Propane Conversion Accessory Kit. For more information, see the Accessories section in the Tech-
nical Guide.
2.
Input rate valid for elevations up to 2000 feet above sea level. For elevations above 2,000 feet, gas input rate should be reduced by 4% for each 1,000 feet above
sea level.
3.
Based on 2500 BTU Per Cu. Ft.
4.
Refer to the Accessories section in the Technical Guide for a brief description of the propane conversion kit.
SECTION V: AIRFLOW PERFORMANCE
Table 11: Airflow Performance - Side Duct Application
Model
Jumper Position
High Cool
Low Cool
36065
High Heat
Low Heat
High Cool
Low Cool
36100
High Heat
Low Heat
Continued on following pages. See end of Table 11 for NOTES.