5 Installation Procedure
4.
Prepare and connect the wire ends as shown in
Wire Gauges, Tightening Torques, and Crimp Terminals on page 21
that the proper tightening torque is applied to each terminal. Take particular
precaution to ensure that each wire is properly connected and wire insulation is not
accidentally pinched into electrical terminals.
WARNING! Fire Hazard. Tighten terminal screws to the specified tightening torque. Loose electrical
connections could result in death or serious injury by fire due to overheating. Tightening screws beyond the
specified tightening torque may cause erroneous operation, damage the terminal block, or cause a fire.
NOTICE: Heat shrink tubing or electrical tape may be required to ensure that cable shielding does not
contact other wiring. Insufficient insulation may cause a short circuit and damage the option or drive.
Figure 6
Figure 7
Preparing wire ends:
Pull back the shielding and lightly
twist the end with fingers, keeping
the ends from fraying.
16
Option terminal
Shield
Figure 6 Preparing Ends of Shielded Cable
about 5.5 mm (7/32")
When not using
crimped insulated
sleeves
Figure 7 Preparing and Connecting Cable Wiring
YASKAWA ELECTRIC TOBP C730600 39B 1000-Series Option DI-A3 Installation Manual
Figure 6
Insulation
Customer-supplied
digital input signal
Shield
Shield sheath
(Insulate with electrical tape
or shrink tubing)
Screwdriver blade size
Blade depth of
0.4 mm or less
Blade width of
2.5 mm or less
Loosen the screws and
insert the wire into the
opening on the terminal block.
Customer-supplied
digital input signal
(do not solder ends)
and
Figure
7.
Refer to
to confirm
Option Terminal block

Advertisement

Table of Contents
loading

This manual is also suitable for:

Di-a3

Table of Contents