Economi$Er ® X (Factory-Installed Option) - Bryant 580J*04A Installation Instructions Manual

580j legacy series single package rooftop with gas heat/electric cooling sizes 04, 05, 06, 07
Table of Contents

Advertisement

Edge Programable Thermostat
O/W2/B
Fig. 35 — 580J Size 07 (unit with Perfect Humidity Dehumidification System) with Edge Programmable Thermostat
ECONOMI$ER
®
X (FACTORY-INSTALLED OPTION)
Product Description — The EconoMi$er X system is an ex-
pandable economizer control system, which includes a W7220
economizer module (controller) with an LCD and keypad (see
Fig. 36). The W7220 can be configured with optional sensors.
Fig. 36 — W7220 Economizer Module
The W7220 economizer module can be used as a stand-
alone economizer module wired directly to a commercial set-
back space thermostat and sensors to provide outside air dry-
bulb economizer control.
Economizer Module — The economizer module is the core of
the EconoMi$er X system. The module is mounted in the unit's
control box, and includes the user interface for the system. The
W7220 economizer module provides the basic inputs and out-
puts to provide simple economizer control. When used with the
optional sensors, the economizer module provides more ad-
vanced economizer functionality.
S-Bus Enthalpy Control Sensors — This sensor is a combina-
tion temperature and humidity sensor which is powered by and
Rc
Rh
W1
G
Y2
C
Y1
OAT
RRS
SRTN
HUM
D1
D2
V+
Vg
Perfect Humidity™ FIOP
communicates on the S-Bus. Up to three sensors may be con-
figured with the W7220 economizer module. See page 23 for
details.
CO
Sensor (optional) — A CO
2
Demand Controlled Ventilation (DCV).
Specifications
W7220 Economizer Module — The module is designed for
use with 2 to 10 Vdc or bus communicating actuator. The mod-
ule includes terminals for CO2 sensor, mixed air sensor, and an
outdoor dry bulb sensor. Enthalpy and other options are avail-
able with bus sensors.
User Interface — Provides status for normal operation, setup
parameters, checkout tests, and alarm and error conditions with
a 2-line 16 character LCD display and four button keypad.
Electrical
Rated Voltage — 20 to 30 Vac RMS, 50/60 Hz
Transformer — 100 va maximum system input
Nominal Power Consumption (at 24 Vac, 60 Hz) — 11.5
VA without sensors or actuators
Relay Digital Output Rating at 30 Vac (maximum power
from Class 2 input only) — 1.5A run:
3.5A inrush at 0.45PF (200,000 cycles) or
7.5A inrush at 0.45PF (100,000 cycles)
External Sensors Power Output — 21 Vdc ± 5% at 48mA
IMPORTANT: All inputs and outputs must be Class 2
wiring.
22
Unit CTB
THERMOSTAT
X*
C
G
W2
W1
Y2
Y1
R
*Connection not required.
sensor can be added for
2

Hide quick links:

Advertisement

Table of Contents
loading