S5-100U
Digital Input Module 8 × 24 V DC
L+
1
F
2
M
4
.0
3
.1
6
.2
5
.3
8
.4
7
.5
10
.6
9
.7
4
DIGITAL INPUT
8 x 24 V DC
6ES5 421-8MA12
1
2
3
4
5
6
180 K
1
3
5
2
4
6
L+
M
X.1 X.0 X.3 X.2 X.5 X.4 X.7 X.6
EWA 4NEB 812 6120-02b
+9 V
GND
Data
7
9
8
10
Technical specifications
Number of inputs
Galvanic isolation
- in groups of
Input voltage L+
- rated value
- "0" signal
- "1" signal
Input current at "1"
signal
typ.
Inherent delay
- from "0" to "1"
typ.
- from "1" to "0"
typ.
Length of cable
- unshielded
max.
Insulation rating
Rated insulation voltage *
(+9 V to
)
- insulation group
Fault LED (red)
Permissible ambient
temperature of module
- horizontal arrangement
- vertical arrangement
Connection of 2-wire
BERO proximity switches
- residual current
Current consumption
from +9 V (CPU)
typ.
Power loss of the
module
typ.
Weight
approx.
* Relevant only for isolated assembly in the
ET 100/200U
Module Spectrum
(6ES5 421-8MA12)
8
no
8
24 V DC
0 to 5 V
13 to 33 V
7 mA at 24 V
2.3 ms
3.5 ms
100 m (330 ft.)
VDE
12 V AC
1×B
no input voltage
L+/M
0 to 60 °C
(32 to 140 °F)
0 to 40 °C
(32 to 104 °F)
possible
1.5 mA
34 mA
1.6 W
190 g (6.7 oz.)
14-17