Table 11-11.
Analog Input Module 464-8MA21, 4x±50 mV "with Linearization"
and "with Temperature Compensation" (Bipolar); Thermoelement Type J
(Iron/Copper-Nickel (Konstantan), according to IEC 584)
Thermal
Units
Voltage
in mV*
1485
1201
1200
69.536
1000
57.942
500
27.388
100
5.268
1
0.05
0
0
-1
-0.05
-100
-4.632
-150
-6.499
-199
-7.868
-200
-7.890
-201
-273
X
*
For a reference temperature of 0° C (32° F)
**
In the overrange area, the current slope of the characteristic curve is maintained when leaving the
linearized nominal range.
EWA 4NEB 812 6120-02b
Temperature
High Byte
° C
° F
0 0 1 0 1 1 1 0 0 1 1 0 1 0 0 1 Overflow
1201
2194
0 0 1 0 0 1 0 1 1 0 0 0 1 0 0 1
1200
2192
0 0 1 0 0 1 0 1 1 0 0 0 0 0 0 0
1000
1832
0 0 0 1 1 1 1 1 0 1 0 0 0 0 0 0
500
932
0 0 0 0 1 1 1 1 1 0 1 0 0 0 0 0
100
212
0 0 0 0 0 0 1 1 0 0 1 0 0 0 0 0
1
34
0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0 Nominal range
0
32
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
-1
-30
1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0
-100
-148
1 1 1 1 1 1 0 0 1 1 1 0 0 0 0 0
-199
-238
1 1 1 1 1 0 1 1 0 1 0 1 0 0 0 0
-200
-326
1 1 1 1 1 0 0 1 1 1 0 0 1 0 0 0
-200
-328
1 1 1 1 1 0 0 1 1 1 0 0 0 0 0 0
-201
-330
1 1 1 1 1 0 0 1 1 0 1 1 1 0 0 1 Overrange
1 1 1 1 0 1 1 1 0 1 1 1 1 0 0 1 Overflow
X
X X X X X X X X X X X X X 0 F 0 Wire break
This value corresponds to the terminal temperature at wire break
Analog Value Processing
Low Byte
Range
Overrange
11-15
**
**