Service Warning - Atlas Copco GA5 User Manual

Stationary air compressors with elektronikon i or ii regulator
Hide thumbs Also See for GA5:
Table of Contents

Advertisement

User manual

6 Service warning

A service warning will appear when the service timer has
reached the programmed time interval.
1. In case the service timer exceeds the programmed time
interval, alarm LED (8) will light up.
2. Press arrow key (12): “r000” is shown (register 000).
Press enter key (5), “S” (S standing for “Service”)
appears. Use key (12) to scroll to “r005” (register 005)
and press enter key (5), the actual reading of the service
timer will be shown in “kHrs” (hours x 1000) .
Example: “4.002” indicates that the compressor has run for
4002 hours since previous service.
3. Press enter key (5) and key (12) to scroll to “r001”
(register 001). Press key (5) to check the running hours,
which are shown in “kHrs” (hours x 1000).
Example of running hours screen:
The screen shows that the number of running hours is 8000.
4. Stop the compressor, switch off the voltage and carry
out the service actions as explained in the maintenance
schedule in the related Instruction book.
Important
-
The “longer interval” service actions must include the
“shorter interval” actions.
In the example above, carry out all service operations
belonging to the 8000 running hours interval as well as
those belonging to the 4000 running hours interval.
-
If using mineral oil instead of Atlas Copco Roto-
injectfluid, the service timer interval has to be decreased:
500 running hours for 13 bar (175 psi) units and 1000
running hours for 7.5-10 bar (100-150 psi) units.
5. After servicing, reset the service timer (see section 7.5).
2920 1461 03
Downloaded from
www.Manualslib.com
kHrs
8.000
manuals search engine
7 Scrolling through all screens
Scroll keys (12 and 13) can be used to scroll through all screens.
The screens are divided in register screens (numbered as “r001”,
“r002”,...) and parameter screens (numbered as “P001”,
“P002”,...).
During scrolling, the numbers of the screens appear consecutively.
For most screens, the unit of measurement and the related
pictograph are shown together with the screen number.
In case of a warning or shut-down, an extra register screen (“r000”)
is accessible.
Example:
kHrs
r001
The screen shows the screen number (“r001”), the unit used (kHrs
or hours x 1000) and the related pictograph for running hours.
Press enter key (5) to call up the actual running hours.
Overview of the screens
Register
Show
screens
r001
Running hours (x1000 hrs)
r002
Loading hours (x1000 hrs)
r003
Motor starts (x1000)
r004
Motor starts (x1)
r005
Service timer reading
r006
Status of function "Automatic restart after voltage
failure"
r007
Programmed set of parameters