External Switching Of Heating Program/External Heat Demand - Viessmann Vitodens 200 WB2 11-44 Installation Instructions Manual

Wb2 series wall-mounted, gas-fired condensing boiler. for natural gas and liquid propane heating input ng 55 to 230 mbh 16 to 67 kw heating input lp 55 to 214 mbh 16 to 63 kw
Hide thumbs Also See for Vitodens 200 WB2 11-44:
Table of Contents

Advertisement

Electrical Connections

External switching of heating program/External heat demand

1.
X4
2.
1 2
3
4
External burner disable
X6
1.
1 2
3
4
(continued)
Control Connections
IMPORTANT
Load capacity of the connection is 10
mA at 24 V–.
For external call for heat function:
See Start-up/Service
Instructions with regard to
changing the coding addresses.
1. Remove jumper between "X4.1" and
"X4.2".
2. Connect switch contact to
connector "X4".
3. Set coding addresses 011, 027, and
0A2.
See Start-up/Service
Instructions with regard to
setting coding addresses.
1. Connect switch contact to connector
"X6".
IMPORTANT
The potential-free contact must be
field supplied.
See Start-up/Service
Instructions regarding
changes to the plug-in
jumper "X6" and coding
addresses.
41