Electrical Connections

Outdoor temperature sensor

1.
1.
2.
2.
(continued)
3.
3.
X6
X6
1 2
1 2
3
3
4
4
1. Remove cover of outdoor
temperature sensor.
2. Mount wall-mount base (cable entry
must point downward).
4.
4.
IMPORTANT
The outdoor temperature sensor
should be mounted 6.6 to 8.2 ft./
2 to 2.5 m above ground level on the
north or northwest wall of the
building. In case of a multi-storey
building, mount outdoor temperature
sensor in the upper half of the
second floor.
Ensure that sensor is not located
above windows, doors and air vents,
or immediately underneath a balcony
or gutter.
The outdoor temperature sensor must
not be covered by plaster. If
mounting on an unplastered wall,
make allowances for thickness of
plaster or remove sensor before
plastering wall.
3. Connect cable to terminals (wires
are interchangeable).
Cable specifications:
2-wire cable, max. cable length
5.
5.
95 ft./35 m with a wire size of min.
AWG 16 copper.
IMPORTANT
Cable to the outdoor sensor must
not be laid near line voltage wiring
(120/240 V).
4. Place cover on base and snap into
place.
5. Connect the outdoor temperature
sensor to terminals "X6.3" and
"X6.4" (wires are interchangeable).
Control Connections
39