Outside Temperature Sensor; External Demand Via Switching Contact; External Demand Via 0 - 10 V Input - Viessmann Vitodens 222-F Installation And Service Instructions For Contractors

Gas condensing storage combi boiler
Table of Contents

Advertisement

Installing the boiler
Electrical connections

Outside temperature sensor

For fitting the wireless outside temperature sensor
(wireless accessory):
Wireless base station installation and service
instructions
Fitting location for outside temperature sensor
North or north-western wall, 2 to 2.5 m above ground
level; in multi storey buildings, in the upper half of the
second floor
Not above windows, doors or vents

External demand via switching contact

Connection options:
EA1 extension (accessory, see separate installation
instructions)
Plug
lH
When the contact is closed, burner operation is load-
dependent. The boiler water is heated to the set value
selected in coding address "9b" in group "General"/1.
The boiler water temperature is limited by this set
value and by the electronic maximum limit (coding
address "06" in group "Boiler"/2).
Plug
lH
A
1 L
N
?
lH
Floating contact (when connected, remove jumper
A
between L and 1)
Codes
"4b:1" in group "General"/1
Effect of the function on the relevant heating circuit
pump:
Coding address "d7" in group "Heating circuit" (only
for weather-compensated control units)
Effect of the function on the circulation pump for cylin-
der heating:
Coding address "5F" in group "DHW"/3
External demand via 0
Connection at 0
10 V input to EA1 extension.
18
(cont.)
!
10 V input
Not immediately below balconies or gutters
Never render over
Outside temperature sensor connection
2-core lead, length max. 35 m with a cross-section of
2
1.5 mm
!
Please note
Live contacts lead to short circuits or phase fail-
ure.
The external connection must be floating and
meet the requirements of protection class II.
EA1 extension
[{A
[{S
DE
DE
A
Floating contact
A
EA1 extension
B
Codes
Set "3A" (DE1), "3b" (DE2) or "3C" (DE3) to 2 in
group "General"/1
Effect of the function on the relevant heating circuit
pump:
Coding address "d7" in group "Heating circuit" (only
for weather-compensated control units)
Effect of the function on the circulation pump for cylin-
der heating:
Coding address "5F" in group "DHW"/3
B
[{D
DE