Installing AC Power Components

Installing AC Power Components
This section provides information and instructions to perform the following:
AC Power Warnings and Notes
Warning:
• Before connecting or disconnecting ground or power wires, make sure that power is removed
from the AC circuit.
Caution:
• This product relies on the building's installation for short-circuit (overcurrent) protection.
Ensure that a circuit breaker, or other equivalent means, no larger than 20A is used in the
building's AC branch circuit for the current carrying conductors.
• There must be no switching or disconnecting devices in the earthed circuit conductor between
the AC source and the point of connection of the earthing electrode conductor.
• This equipment has a high leakage current due to multiple AC power modules. Connect each
power entry module to a separate branch circuit with proper earth ground connections.
Notes:
If you intend to use AC power entry modules in the 7450 ESS-7, observe the following
guidelines:
• AC power modules operate with a nominal utility system voltage of 200V to 240V, but will
operate with input voltages ranging from 175 to 264 VAC.
• A fully redundant AC system must have two AC power entry modules and two AC-to-DC
power converters installed and operational.
• Each AC PEM contains an AC plug receptacle to accept an AC power cord. The other end of
the AC power cord must have a plug that fits into the power source receptacle that is standard
for your geographic region.
• Each AC-input PEM requires a dedicated 20A service.
• For a listing of the electrical specifications for the AC-input power module, see
Specifications on page
• The remote power source (circuit breaker panel, outlet, etc.) must be easily accessible.
Page 72
AC Power Warnings and Notes on page 72
Installing an AC PSM on page 73
Installing an AC PEM on page 77
Connecting the AC Power Cord on page 79
40.
Power Module
7450 ESS-7