IBM iDataPlex Rack Type 7825 Installation And Service Manual page 20

Data center solution
Table of Contents

Advertisement

Space between iDataPlex racks
Space between iDataPlex racks in series
600 mm
(23.6 in)
When you attach iDataPlex rack cabinets together to form a suite of rack cabinets, you must keep a minimum
distance between suites in the same room. This distance provides proper ventilation and allows access to install
and service optional devices.
Notes:
1. The access space that is needed to service the rack depends on the devices that are installed and your installation and
2. For this layout, rear door heat exchangers must be installed.
** Depending on floor tile size. (European = 600 mm x 600 mm, English = 24 in. x 24 in.).
Figure 2. Leaving space between rack cabinet suites
The internal dimensions of the rack cabinet conform to the EIA standard EIA-310-D
Cabinets, Racks, Panels, and Associated Equipment (1992). See Figure 3 on page
9 for rack cabinet internal dimensions.
8
IBM iDataPlex Cluster Solution: Installation and Service Guide
Note: Guidelines for space between racks:
• 600 mm or 24 in (no rear door heat exchangers installed)
• 1200 mm or 48 in (rear door heat exchangers installed)
** Depending on floor tile size. (European = 600 mm x 600 mm, English = 24 in. x 24in. )
service agreement. Unless your installation and service agreement specifies a smaller access space, use the distance guidelines
in Figure 2.
Either
1200 mm
or 48 in **
Either
1200 mm
or 48 in **
600 mm
(23.6 in)
See Note
Either
1200 mm
or 48 in
Either
1200 mm
or 48 in
Either
1200 mm
or 48 in