ABB i-bus KNX Product Manual page 94

Dali-light controller dlr/a 4.8.1.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus
KNX
Commissioning
Reaction on DALI voltage or light
controller supply voltage recovery
Options:
This parameter determines the state that the function Staircase lighting assumes after DALI or light
controller supply voltage recovery.
After a DALI or light controller supply voltage recovery, the lighting group assumes the state as
parameterized in parameter window
parameterized for the function Staircase lighting:
not activated: The function Staircase lighting is not reactivated after DALI or light controller supply
voltage recovery. The lighting group behaves like a normal lighting group without additional functions.
activate standby: The function Staircase lighting is activated after DALI or light controller supply
voltage recovery and is in standby. The lighting group can be started by an ON telegram or a renewed
activation via the communication object Stairc. light. activate/status.
92 2CDC507128D0202 | DLR/A 4.8.1.1
Relative dimming
Options:
no reaction
set function in standby
With activated function Staircase lighting, the parameter can be used to define the reaction to
dimming telegram to the communication object Relative dimming.
no reaction: Dimming telegrams are ignored.
set function in standby: A dimming telegram ends function Staircase lighting, and the lighting
group carries out the dimming telegram. The function Staircase lighting is latent and waits until
a renewed activation via the communication object function Stairc. light. activate/status or via
an ON telegram to the communication object Switch.
Recall scene
Options:
no reaction
set function in standby
With activated function Staircase lighting, the parameter can be used to define the reaction to a
scene recall on the communication object Recall scene.
no reaction: A scene recall is ignored.
set function in standby: A scene recall ends the function Staircase lighting, and the DLR/A
carries out the dimming telegram. The function Staircase lighting is latent and waits until a
renewed activation via the communication object function Stairc. light. activate/status or via an
ON telegram to the communication object Switch.
not activated
activate standby
activate and ON
previous state to malfunction
Parameter window - Gx
Fault, page 77. The following states can be

Advertisement