ABB i-bus
KNX
Commissioning
"Request status values"
Options:
Via this communication object, all status messages can be requested, provided that they have been
parameterized with the option after a change or request or only after request.
no: The 1 bit communication object Request status values is not enabled.
yes: A 1 bit communication object Request status values is enabled. The following parameter
appears:
Enable staircase lighting time curve
(one curve per gateway)
Options:
The DLR/A has the option of implementing a staircase time curve incorporating a dimming up and pre-
warning phase. This curve can be recalled individually, however, for every lighting group with the switch
telegram of the lighting group. The staircase time curve is defined in the next parameter that appears with
the option yes.
no: In the DLR/A, Staircase lighting is not available.
yes: The DLR/A has a Staircase lighting function. A time curve is defined in the next parameters.
44 2CDC507128D0202 | DLR/A 4.8.1.1
no
yes
Request with object value
Options:
0
1
0 or 1
This parameter defines the value at which the communication object Request status values is
triggered. With this function, an opportunity is presented, e.g. to provide up-to-date values to a
visualization system.
0: Sending status messages is requested with the value 0.
1: Sending status messages is requested with the value 1.
0 or 1: Sending status messages is requested with the values 0 or 1.
no
yes
Scenes 13 and 14 are used for function staircase lighting
Note
If the function Staircase lighting is used in the DLR/A, the scenes 13 and 14 are used for this
function. These are then no longer available as "normal" scenes.