KNX
Commissioning
No.
26
This communication object is enabled if in
Burn-in object "Burn-in lamp/status" is parameterized with the option yes and a status message about the burn-in process
is also required.
The communication object also features in addition to the properties of the communication object Burn-in lamp are
previously described, the property that the burn-in status can be requested or sent on the KNX in accordance with the
parameterization.
Telegram value:
27
This communication object is always enabled; however, it is only required for the artificial lighting and daylight calibration of
a constant lighting control.
Using this communication object, the communication objects Daylight calibration or Artificial lighting calibration are enabled
for receipt of a telegram, i.e., the DLR/A only performs a daylight or artificial lighting calibration if the communication object
Enable controller calibration has received a telegram with the number of the respective lighting group (1...4) beforehand.
This ensures that calibration is not performed unintentionally.
The readiness to receive a telegram for activation of the daylight or artificial lighting calibration remains in effect for 1 hour,
if a calibration request has not been received and has taken place beforehand via the communication objects Calibration
artificial light or Calibration daylight.
Telegram value:
Function
Burn-in lamp/status
Parameter window
0 = deactivate burn-in function or no lighting group is in the burn-in state.
1 = activate Burn-in function or at least one lighting group is in the burn-in state.
Enable controller calibration
1...4 = The number value enables the lighting group via the communications objects,
to perform a Calibration artificial light or Calibration daylight of the constant lighting
control
0 =
Immediately resets the readiness to receive for the communication objects Calibration
daylight and Calibration artificial light, i.e. telegrams to the communication objects
Calibration artificial light or Calibration daylight are not actioned.
Object name
DALI output
Central, page 49, the parameter Enable central function lamp
DALI output
DLR/A 4.8.1.1 | 2CDC507128D0202 137
Data type
Flags
1 bit
C, W
DPT 1.010
1 byte
C, W
non DPT

Advertisement

Table of Contents