ABB i-bus
KNX
Commissioning
"Fault DALI"
Options:
Using this communication object, a fault of the DALI communication of the output, i.e. a short-circuit
> 500 ms or a data collision, can be sent or read, e.g. for diagnostic purposes. Individual fault indication
objects are available for a ballast/lamp fault.
no: The communication object Fault DALI is not enabled.
yes: The communication object Fault DALI is enabled. As soon as there is a DALI fault on the output,
it is indicated by a 1 in the communication object Fault ballast. The following parameter appears:
"Fault lamp"
Options:
Via this communication object, a fault of a lamp for the DALI output can be sent or read.
no: The communication object Fault lamp is not enabled.
yes: The communication object Fault lamp is enabled. As soon as there is a lamp fault on the output,
it is indicated by a 1 in the communication object Fault lamp. The following parameter appears:
60 2CDC507128D0202 | DLR/A 4.8.1.1
Send
Options:
after a change
after request
after a change or request
after a change: The status is sent via the communication object after a change.
after request: The status is sent after a request by the communication object Request status
values.
after a change or request: The status is sent via the KNX when the status changes or the
status is requested via the communication object Request status values.
no
yes
Send
Options:
after a change
after request
after a change or request
after a change: The status is sent via the communication object after a change.
after request: The status is sent after a request by the communication object Request status
values.
after a change or request: The status is sent via the KNX when the status changes or the
status is requested via the communication object Request status values.
no
yes