ABB i-bus
KNX
Commissioning
Group x Brightness value of Scene (x = 1...16)
Options:
Note
The options 100 % (255) to 0 % (OFF) are only visible if the parameter Overwrite scene on download is
set to yes. With the option no, the possible settings are reduced to no change (no member in this scene)
and member in this scene.
This parameter defines the brightness value that is set in the lighting group when a scene is recalled.
no change (not a member in this scene): This lighting group is not included in this scene. During a
Recall scene, the lighting group is not influenced. The current brightness value of the lighting group
remains unchanged and even when the scene is stored via the KNX, the brightness value of this
group is not stored.
100 % (255)...0 % (OFF): The lighting group belongs to the scene. During a Recall scene, the lighting
group is set to the parameterized brightness value here. If the set brightness value is above or below
the set maximum or minimum brightness value of the respective lighting group (see
window Gx
116 2CDC507128D0202 | DLR/A 4.8.1.1
no change (not a member in this scene)
100 % (255)
99 % (252)
...
1 % (3)
0 % (OFF)
Group, page 63), the respective brightness value is saved in the scene.
Parameter