A.
Emergency Stop Error
Indicates an emergency stop error.
Receptacle RC5-1 connects to receptacle RC1-4 and receptacle RC5-2 connects to receptacle RC4-2 on E-Stop board
PC12. A closure between RC4-1 and RC4-2 allows +24 volts DC to be supplied to the four relays on E-Stop board PC12.
In an E-Stop situation (relays open), all four relays on the E-Stop board de-energize and cut power to the control boards.
When relay CR1 on E-Stop board PC12 is de-energized, it drops out the 18 volts AC from transformer T1 that powers the
E
inverter control board(s).
When relay CR2 on E-Stop board PC12 is de-energized, it breaks the contactor signal being sent to the inverter engine
STOP
board(s) from the process control module PC4 (J2-9 to RC2-3) and causes a loss of signal to the AIM board (RC2-1 and
RC2-2) and to micro input (RC5-3 and RC5-4), signaling an E-Stop is active.
When relay CR3 on E-Stop board PC12 is de-energized, it breaks the secondary side output of the motor board before it
goes to the filter board.
Relay CR4 on E-Stop board PC12 is a soft start relay in parallel with the contacts of relay CR1.
B.
Arc Error
ERR
Indicates voltage has exceeded the programmable limit of a valid arc for the programmed amount of time (default time is
500 ms). Check contact tip, weld conditions, and shielding gas.
Arc error can be enabled or disabled using an optional PDA with File Management/WaveWriter software.
ARC
C.
No Coolant Flow Error
ERR
Indicates no coolant flow in water flow switch option. The error may be reset by reestablishing coolant flow to the gun, and
then pressing the Jog/Purge button.
COOL
D.
Ground Current Detect Error
ERR
Indicates that weld current is flowing through the primary ground. This is a latching error and welding power source power
must be cycled off and back on again.
GND
E.
Line Error
Indicates that primary power has dropped below the operating point of the welding power source. Signal is sent from in-
verter engine module(s) (RC6, Pin 9 on inverter control board PC1) to process control module PC4 (J2, Pin 1). Check for a
ERR
brown-out condition. The primary boost capacitors have dropped below an acceptable minimum voltage threshold.
This circuit monitors the 940 volts primary DC bus voltage across the electrolytic capacitors C1 and C2. Low line is dis-
played when this voltage drops below 858 volts DC. This could happen when attempting to draw near rated output power
LINE
with an input voltage below 190 volts AC, three phase. This causes the boost section to go into current limit trying to sup-
ply the output power. Once current limit is reached, the boost section can no longer hold the bus capacitors at 940 volts
DC. The inverter control will also go into an output current limit mode in an attempt to supply output power.
F.
Motor Over Current Error
ERR
Indicates that the motor has been drawing too much current for too long a time period. To remedy this fault, reduce the wire
feed speed or the wire feeder torque load/duty cycle. Press Jog/Purge button to clear error.
MOTR