Apply the rated control circuit supply voltage 
(24 V AC/DC ... 230 V AC/DC) at terminal blocks A1/A2.
The Power LED lights up.
Close the sensor circuit at S10/S11/S12/S13 and 
S21/S22 as per the wiring.
The IN1/2 LED lights up.
Single or two-channel sensor circuit:
→ Section 12.1, „Signal generator connection versions",
page22.
Automatic start
The enabling current paths 13/14, 23/24 and 33/34 close.
The K1 and K2 LEDs light up.
Signaling current path 41/42 opens.
Manual, monitored start
Press the reset button.
Release the reset button.
The enabling current paths 13/14, 23/24 and 33/34 close.
The K1 and K2 LEDs light up.
Signaling current path 41/42 opens.
Manual ESR5-NO-31-UC 07/2017 MN049014 EN www.eaton.com