Eaton ESR5-NO-31-UC Manual page 20

Safety relay
Table of Contents

Advertisement

7.1 Insolation coordination
16
A1/A2
Logik
6 kV 
A1/A2
-
ST
Logik
-
-
13/14
-
-
23/24
-
-
33/34
-
-
41/42
-
-
Key:
BI
Basic insulation
ST
Safe isolation
BASIC ISULATION
(rated surge voltage of 4 kV)
A mixture of SELV and PELV is strictly prohibited. Only switch
230 V AC at one of the enable contacts if the adjacent contact
carries the same potential.
Safe isolation/reinforced insulation
(rated surge voltage of 6 kV)
Reinforced insulation (e.g., thanks to greater air clearances and
creepage distances between conductive paths) is designed for
one overvoltage category higher than basic insulation. This
means that SELV circuits of U ? 25 V AC or U ? 60 V DC and cir-
cuits with higher voltages can be mixed.
Manual ESR5-NO-31-UC 07/2017 MN049014 EN www.eaton.com
13/14
23/24
33/34
6 kV 
6 kV 
6 kV 
ST
ST
ST
6 kV 
6 kV 
6 kV 
ST
ST
ST
6 kV 
6 kV 
-
ST
ST
-
-
4 kV
BI
-
-
-
-
-
-
41/42
6 kV 
ST
6 kV 
ST
6 kV 
ST
4 kV
BI
4 kV
BI
-

Hide quick links:

Advertisement

Table of Contents
loading