16.5 Single-channel emergency stop monitoring

32
Single-channel emergency stop monitoring
Manual, monitored start
Monitoring of external contactors (optional)
No cross-circuit detection in the sensor circuit
Suitable up to category 1, PL c (EN ISO 13849-1), SIL 1 (EN 62061)
Feedback from contactor K1 is not essential in order to achieve
category 1.
L
24-230V AC /DC
S1
S
11
S
10
A1
(+)
( )
ESR5-...
A2
S2
M
(N )
Figure 18:
Single-channel emergency stop monitoring/manual, monitored start
Key:
S1
Emergency stop button
S2
Manual reset device
K1
Contactor
Manual ESR5-NO-31-UC 07/2017 MN049014 EN www.eaton.com
S1 2
S
13
S2 2
S
2 1
( )
( )
( )
(GND)
( )
( )
S3 4
S3 5
1 4
K1
K1
13
23
33
41
K1
2 4
3 4
4 2
M