Eaton ESR5-NO-31-UC Manual page 13

Safety relay
Table of Contents

Advertisement

Conformance/Approvals
Conformance
The full EC Declaration of Conformity can be downloaded for the product at www.eaton.eu/esr5.
Approvals
Safety data
Stop category according to IEC 60204
Safety parameters for IEC 61508 - High Demand
SIL
PFHD
Demand rate
Proof test intervall
Duration of use
Safety parameters for IEC 61508 - Low Demand
SIL
PFDavg
Proof test intervall
Duration of use
Safety characteristic data according to EN ISO 13849
Category
Performance Level
Duration of use
For applications in PL e, the required demand rate for the safety function is once per month
Safety parameters for EN 62061
SILCL
Manual ESR5-NO-31-UC 07/2017 MN049014 EN www.eaton.com
CE-compliant
0
3
1,00 x 10-9 (5 A DC13; 5 A AC15; 8760 switching cycles/year)
< 12 Months
240 Months
240 Months
3
1,49 x 10-4
56 Months
240 Months
4 (5 A DC13; 5 A AC15; 8760 switching cycles/year)
e
240 Months
3
9