Figure 17 Antenna Replacement - Honeywell XYR 6000 User Manual

Onewireless wcx series wireless valve position sensor
Hide thumbs Also See for XYR 6000:
Table of Contents

Advertisement

Step
NOTE: Honeywell recommends lubricating the cover O-ring (13) and threads with a Silicone
14
Grease such as Dow Corning #55 or equivalent before replacing the cover.
Replace cover, tightening hand tight. If applicable, replace cover lock clamp and two T-15
TORX screws.
Return sensor to service.
If the unit removal or re-installation caused the input shaft to be rotated enough to make the
15
internal slip clutch slip, then re-setting the device angle must be performed (see section 3).
For elbow type antenna, adjust antenna for best reception. Don't rotate antenna more than 180
16
degrees either direction or you could twist and break the antenna wiring inside. Tighten the
antenna locking set screw (10).
Revision 1
OneWireless XYR 6000 Wireless Valve Position Sensor User's Manual
1/15/09
Action

Figure 17 Antenna Replacement

6. 5BMaintenance/Repair
6.2. Replacing Antenna
43

Advertisement