Preparation; Battery Connecting Procedure - Honeywell XYR 6000 User Manual

Onewireless wcx series wireless valve position sensor
Hide thumbs Also See for XYR 6000:
Table of Contents

Advertisement

3.1

Battery Connecting Procedure

WARNING
Risk of death or serious injury from explosion or fire.
Connection and disconnection of the batteries should be done only when the
area is non-hazardous.
WARNING
Risk of death or serious injury from explosion or fire.
If sensor is to be returned to Honeywell for any reason, both batteries MUST
be removed prior to shipping. Dispose of used batteries promptly per local
regulations or the battery manufacturer's recommendations. Keep away from
children. Do not disassemble and do not dispose of in fire.
ATTENTION
Both batteries must be the same model from the same manufacturer. Mixing
old and new batteries or different manufacturers is not permitted.
Use only the following 3.6V lithium thionyl chloride (Li-SOCl2) batteries (non-
rechargeable), size C. No other batteries are approved for use in WCX Series
Valve Position Sensors.
Xeno Energy XL-145F
Tadiran TL-5920/S
Step
If applicable, remove two T-15 TORX screws (1) and cover lock clamp (2).
1
If necessary, place a large screwdriver or other flat tool across the two tabs on the cover (3).
2
Unscrew and remove the cover.
Using two fingers, press down slightly on both battery tops (4) and remove battery insulator
3
(5). Insure that the batteries are properly seated and making good contact.
Replace cover, tightening hand tight. If applicable, replace cover lock clamp (2) and two T-15
4
TORX screws (1).
Revision 1
OneWireless XYR 6000 Wireless Valve Position Sensor User's Manual
1/15/09

3. Preparation

Table 1 Battery Connecting Procedure
(For item numbers, refer to Figures 2 and 3)
3.1. Battery Connecting Procedure
Action
3. 2BPreparation
9