6. 5BMaintenance/Repair
6.1. Replacing Batteries
6.1
Replacing Batteries
When to replace
When the sensor displays a LOW BAT message you have 2-4 weeks to replace both batteries before they
expire. When batteries are removed or expired, all sensor data is retained in the Radio Board's non-volatile
memory. All calibration data is retained in the Measurement Board's non-volatile memory, however, if the
sensor was physically removed and re-installed, the calibration must be re-checked.
Tools required
•
T-15 Security TORX Screwdriver (Bit supplied with Product) (if applicable)
•
#2 Phillips Screwdriver or 1/4" Slotted Screwdriver
•
Torque Screwdriver
•
Large screwdriver or other flat tool
•
Heavy tweezers or needle-nose pliers
Procedure
ATTENTION
Batteries must be replaced only by a trained service technician.
WARNINGS
•
•
•
•
•
36
OneWireless XYR 6000 Wireless Valve Position Sensor User's Manual
6. Maintenance/Repair
Figure 14 Low Battery Warning
Risk of death or serious injury by explosion. Do not open sensor
enclosure when an explosive gas atmosphere is present.
Batteries must not be changed in an explosive gas atmosphere.
The batteries used in this device may present a risk of fire or chemical
burn if mistreated. Do not recharge, disassemble, heat above 100°C
(212°F), or incinerate.
When installing batteries, do not snag the battery terminal on the clip or
the battery may be damaged. Do not apply excessive force.
Do not drop. Dropping the battery may cause damage. If a battery is
dropped, do not install the dropped battery into the sensor. Dispose of
dropped battery promptly per local regulations or per the battery
manufacturer's recommendations.
Revision 1
1/15/09