Keypad Panic Options - Paradox Digiplex Reference & Installation Manual

Hide thumbs Also See for Digiplex:
Table of Contents

Advertisement

Recognition) if a tamper or wire fault occurs on a
bypassed zone.
8.4 K
P
EYPAD
ANIC
Sections [506], [510], [514], [518] - Options [1] to [6]
As the control panel can enable Keypad Panic
Options for each individual partition, select the
section that corresponds to the desired partition and
set options [1] through [6] on/off to obtain the desired
options as described below.
Option [1]
– P
ON
ANIC
Pressing the [1] & [3] keys simultaneously on the
keypad for 2 seconds will generate a silent or audible
alarm as defined by option [4].
Option [2]
– P
ON
ANIC
Pressing the [4] & [6] keys simultaneously on the
keypad for 2 seconds will generate a silent or audible
alarm as defined by option [5].
Option [3]
– P
ON
ANIC
Pressing the [7] & [9] keys simultaneously on the
keypad for 2 seconds will generate a silent or audible
alarm as defined by option [6].
O
PTIONS
1
2
3
Option [4]
= Panic 1 – Silent
ON
= Panic 1 – Audible
OFF
Option [5]
= Panic 2 – Silent
ON
= Panic 2 – Audible
OFF
Option [6]
= Panic 3 – Silent
ON
= Panic 3 – Pulsed (Fire)
OFF
Silent operation:
The control panel emits a single confirmation beep
and transmits the appropriate report code (see
section 9.2.5) to the central station.
Audible operation:
The alarm output (bell/siren) activates until a user
cancels the alarm with a valid User Access Code or
when the Bell Cut-Off Timer elapses (see section 8.2).
Fire operation:
Same as audible operation, except that the
bell/siren output will be pulsed as shown in figure
5.3 on page 17.
- 27 -