Paradox DIGIPLEX DGP-NE96 Programming Manual
Paradox DIGIPLEX DGP-NE96 Programming Manual

Paradox DIGIPLEX DGP-NE96 Programming Manual

96-zone expandable security and access control panel
Hide thumbs Also See for DIGIPLEX DGP-NE96:

Advertisement

96-Zone Expandable Security and Access Control Panel
Default Installer Code
000000
(To modify the installer code, refer to section [1000], Installer Code Programming on page 22)
Default System Master Code
1234
123456
or
How Do I Enter Programming Mode?
1)
Press and hold the [0] key.
2)
Enter your [
INSTALLER CODE
3)
Enter 4-digit [
].
SECTION
4)
Enter required [
].
DATA
Decimal and Hexadecimal Programming Table
Certain sections may require the entry of one or more Hexadecimal values from 0 to F.
For LCD keypads:
Key
[0] to [9]
0 to 9 (Hex & Decimal)
[
]
A (Hex Only)
STAY
[
]
B (Hex Only)
FORCE
[
]
C (Hex Only)
ARM
[
]
D (Hex Only)
DISARM
For Grafica keypads:
[0] to [9]
= values 0 to 9 respectively
[#]
= A to F (press the [#] key until the
desired letter appears)
Programming Guide V1.5
].
Value or Action
(DGP-NE96)
Key
[
]
E (Hex Only)
BYP
[
]
F (Hex Only)
MEM
[
]
Exit section without saving (Hex & Decimal)
CLEAR
[
]
Save current data and advance to next section (Hex Only)
ENTER
Right Action Key (Exit)
Center Action Key (Save)
www.paradox.ca
DGP-NE96
Value or Action
= Exit section without saving
= Save current data and advance to next
section

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the DIGIPLEX DGP-NE96 and is the answer not in the manual?

Questions and answers

Summary of Contents for Paradox DIGIPLEX DGP-NE96

  • Page 1 = values 0 to 9 respectively Right Action Key (Exit) = Exit section without saving = A to F (press the [#] key until the Center Action Key (Save) = Save current data and advance to next desired letter appears) section www.paradox.ca...
  • Page 2 Digiplex DGP-NE96 - 2 - Programming Guide...
  • Page 3: Table Of Contents

    Other Options ............................. 31 Communication Settings ........................32 System Event Call Direction......................33 Partition Settings..........................34 Special and Trouble Report Codes....................39 Other Settings and Modes......................... 40 Control Panel Hardware Connections....................46 Trouble Display ..........................53 Digiplex DGP-NE96 - 3 - Programming Guide...
  • Page 4: Serial Number List

    5:______________________________________ 20:_____________________________________ 35:_____________________________________ 6:______________________________________ 21:_____________________________________ 36:_____________________________________ 7:______________________________________ 22:_____________________________________ 37:_____________________________________ 8:______________________________________ 23:_____________________________________ 38:_____________________________________ 9:______________________________________ 24:_____________________________________ 39:_____________________________________ 10:_____________________________________ 25:_____________________________________ 40:_____________________________________ 11:_____________________________________ 26:_____________________________________ 41:_____________________________________ 12:_____________________________________ 27:_____________________________________ 42:_____________________________________ 13:_____________________________________ 28:_____________________________________ 43:_____________________________________ 14:_____________________________________ 29:_____________________________________ 44:_____________________________________ 15:_____________________________________ 30:_____________________________________ 45:_____________________________________ Digiplex DGP-NE96 - 4 - Programming Guide...
  • Page 5 51:______________________________________ 67:_____________________________________ 83:_____________________________________ 52:______________________________________ 68:_____________________________________ 84:_____________________________________ 53:______________________________________ 69:_____________________________________ 85:_____________________________________ 54:______________________________________ 70:_____________________________________ 86:_____________________________________ 55:______________________________________ 71:_____________________________________ 87:_____________________________________ 56:______________________________________ 72:_____________________________________ 88:_____________________________________ 57:______________________________________ 73:_____________________________________ 89:_____________________________________ 58:______________________________________ 74:_____________________________________ 90:_____________________________________ 59:_____________________________________ 75:_____________________________________ 91:_____________________________________ 60:_____________________________________ 76:_____________________________________ 92:_____________________________________ 61:_____________________________________ 77:_____________________________________ 93:_____________________________________ Digiplex DGP-NE96 - 5 - Programming Guide...
  • Page 6 106:_____________________________________ 118:_____________________________________ 95:_____________________________________ 107:_____________________________________ 119:_____________________________________ 96:_____________________________________ 108:_____________________________________ 120:_____________________________________ 97:_____________________________________ 109:_____________________________________ 121:_____________________________________ 98:_____________________________________ 110:_____________________________________ 122:_____________________________________ 99:_____________________________________ 111:_____________________________________ 123:_____________________________________ 100:_____________________________________ 112:_____________________________________ 124:_____________________________________ 101:_____________________________________ 113:_____________________________________ 125:_____________________________________ 102:_____________________________________ 114:_____________________________________ 126:_____________________________________ 103:_____________________________________ 115:_____________________________________ 127:_____________________________________ 104:_____________________________________ 116:_____________________________________ 105:_____________________________________ 117:_____________________________________ Digiplex DGP-NE96 - 6 - Programming Guide...
  • Page 7: Zone Programming

    Zone Programming Zone Numbering Zone Parameters Keypad Detector A Hardwired Keypad Zone SN#: 1A000252 SN#: 21000033 Sections [0001] to [0096] represent zones Device A Sections [0101] to [0196] represent zones 1 through 96. This feature defines the 1 through 96. This feature allows you to type of zone, its partition assignment and the zone’s options.
  • Page 8 Zone Description Module Section 8-digit Serial Number Input# Section Define Assign Zone Options [0024] [0124] ________________________ _______________ ___/___/___/___/___/___/___/___ ___/___/___ 1 2 3 4 5 6 7 8 [0025] [0125] ________________________ _______________ ___/___/___/___/___/___/___/___ ___/___/___ 1 2 3 4 5 6 7 8 [0026] [0126] ________________________ _______________...
  • Page 9 Zone Description Module Section 8-digit Serial Number Input# Section Define Assign Zone Options [0064] [0164] ________________________ _______________ ___/___/___/___/___/___/___/___ ___/___/___ 1 2 3 4 5 6 7 8 [0065] [0165] ________________________ _______________ ___/___/___/___/___/___/___/___ ___/___/___ 1 2 3 4 5 6 7 8 [0066] [0166] ________________________ _______________...
  • Page 10: Zone Report Codes

    Zone Report Codes Ademco slow, Silent Knight fast, SESCOA, Ademco express or Pager formats: Key-in desired 2-digit hex values from 00 to FF. Ademco format: Use section [4032] to program a set of default Ademco report codes from the Automatic Report Code Programming on page 41. Then to program the remaining report codes or to change some of the defaults, enter the individual sections and key-in the desired 2-digit hex value found in the Contact ID Report Code List on page 44.
  • Page 11 [0247] Zone 47 __/__ __/__ __/__ __/__ [0272] Zone 72 __/__ __/__ __/__ __/__ [0248] Zone 48 __/__ __/__ __/__ __/__ [0273] Zone 73 __/__ __/__ __/__ __/__ [0249] Zone 49 __/__ __/__ __/__ __/__ [0274] Zone 74 __/__ __/__ __/__ __/__ [0250]...
  • Page 12: Zone Labels

    Zone Labels Section Zone # Zone Label Section Zone # Zone Label Section Zone # Zone Label [0301] Zone 1 [0306] Zone 6 [0311] Zone 11 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [0302] Zone 2 [0307] Zone 7 [0312] Zone 12 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [0303] Zone 3...
  • Page 13: Keyswitch Programming

    Keyswitch Programming Keyswitch Description Module Section 8-digit Serial Number Input# Section Define Assign Keyswitch Options [0501] ___/___/___/___/___/___/___/___ ___/___/___ [0601] _______________________ _______________ 4 5 6 7 8 [0502] ___/___/___/___/___/___/___/___ ___/___/___ [0602] _______________________ _______________ 4 5 6 7 8 [0503] ___/___/___/___/___/___/___/___ ___/___/___ [0603] _______________________ _______________ 4 5 6 7 8...
  • Page 14 Keyswitch Description Module Section 8-digit Serial Number Input# Section Define Assign Keyswitch Options [0523] ___/___/___/___/___/___/___/___ ___/___/___ [0623] _______________________ _______________ 4 5 6 7 8 [0524] ___/___/___/___/___/___/___/___ ___/___/___ [0624] _______________________ _______________ 4 5 6 7 8 [0525] ___/___/___/___/___/___/___/___ ___/___/___ [0625] _______________________ _______________ 4 5 6 7 8 [0526] ___/___/___/___/___/___/___/___...
  • Page 15: Programmable Outputs

    TLM Trouble (See NOTE 3 on page 21) Smoke detector reset Arm with no entry delay Arm in Stay mode Non-reportable Event Arm in Away mode Full arm when in Stay mode Voice module access Remote control access Digiplex DGP-NE96 - 15 - Programming Guide...
  • Page 16 User Codes 768 to 999 000 to 231 000 to 231 Any User Code Not Used Not Used Keyswitch numbers 001 to 032 001 to 032 Disarm with Keyswitch Any keyswitch Not Used Not Used Digiplex DGP-NE96 - 16 - Programming Guide...
  • Page 17 User Codes 001 to 255 001 to 255 001 to 255 Duress Alarm by User User Codes 256 to 511 000 to 255 000 to 255 User Codes 512 to 767 000 to 255 000 to 255 Digiplex DGP-NE96 - 17 - Programming Guide...
  • Page 18 Power up after total power down Software reset (Watchdog) Test Report Future Use Special Events WinLoad In (connected) WinLoad Out (disconnected) Installer in programming Installer out of programming Any Special Event Not Used Not Used Digiplex DGP-NE96 - 18 - Programming Guide...
  • Page 19 (see Note 4 on page 21) Fire Delay Engaged See Note 1 Status 3 Auto Arm on page 21 Arming with Voice Module (set until Exit Delay finishes) Tamper †: See page 21 : See page 21 Digiplex DGP-NE96 - 19 - Programming Guide...
  • Page 20 005 = Partition 5 007 = Partition 7 255 = Occurs in at least one partition enabled in the system. 002 = Partition 2 004 = Partition 4 006 = Partition 6 008 = Partition 8 Digiplex DGP-NE96 - 20 - Programming Guide...
  • Page 21 Utility Key Event 63 KS** Input 32 opens Utility Key Event 64 KS** Input 32 closes ** Keyswitch ‡ Refer to the MG-RCV3 Reference and Installation Manual for remote control button programming instructions. Digiplex DGP-NE96 - 21 - Programming Guide...
  • Page 22 __/__/__ (001 to 255) x 30 msec. 24 (ATZ DGP2-ZX4 I 600 msec. NPUT PEED OF NPUT NPUT Installer Code Programming Section Data Description Default [1000] __/__/__/__/__/__ 000000 NSTALLER [3001], Installer lock REFER TO SECTION ON PAGE Digiplex DGP-NE96 - 22 - Programming Guide...
  • Page 23: User Code Options

    Grafica keypad, refer to Grafica’s User Manual. A complete Grafica User Manual is available on our Web site at www.paradox.ca. To program user labels, refer to the LCD Keypad System Manager’s Manual.
  • Page 24: Arming And Disarming Report Codes

    __/__ Access Code 12 [2118] __/__ Access Code 18 [2124] __/__ Access Code 24 [2125] __/__ Access Code 25 [2144] __/__ Access Code 44 [2163] __/__ Access Code 63 [2182] __/__ Access Code 82 Digiplex DGP-NE96 - 24 - Programming Guide...
  • Page 25: Access Control Sections

    1 2 3 4 5 * * * [2317] __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ Door 18 [2218] __/__/__/__/__/__/__/__ [2268] 1 2 3 4 5 * * * [2318] __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ Door 19 [2219] __/__/__/__/__/__/__/__ [2269] 1 2 3 4 5 * * * [2319] __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ Digiplex DGP-NE96 - 25 - Programming Guide...
  • Page 26 ___ ___ : ___ ___ ___ ___ : ___ ___ Schedule B ___ ___ : ___ ___ ___ ___ : ___ ___ [2413] Schedule A ___ ___ : ___ ___ ___ ___ : ___ ___ Digiplex DGP-NE96 - 26 - Programming Guide...
  • Page 27 Schedule A: Start Time 22:00 and End Time 23:59 then program Schedule B Start Time 00:00 and End Time 06:00. The schedule will not be interrupted between 23:59 and 00:00. Digiplex DGP-NE96 - 27 -...
  • Page 28 December 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 * Digiplex DGP-NE96 - 28 - Programming Guide...
  • Page 29: Keypad Numbering

    * Please note that when the Combus Speed is changed, all operations on the system will be suspended for approximately 1 minute while the system configures itself. † A 40VA transformer is required when selecting the 850mA battery charge current. Using a 20VA transformer with a battery charge current of 850mA may damage the system. Digiplex DGP-NE96 - 29 - Programming Guide...
  • Page 30: Dialer Options

    Force dial Switch to pulse dialing on 5 attempt Bell/siren upon communication Enabled Report zone restore Enabled Disabled Disabled failure if system is armed ON = On zone closure; OFF = On bell cut-off Digiplex DGP-NE96 - 30 - Programming Guide...
  • Page 31: Other Options

    00 : 00 UTO TEST REPORT TIME OF DAY [3042] __/__/__ (000 - 255 x 1 minute) 5 minutes RMED REPORT DELAY [3043] __/__/__ (000 - 255 x 1 minute) 60 minutes ISARMED REPORT DELAY Digiplex DGP-NE96 - 31 - Programming Guide...
  • Page 32: Communication Settings

    EPORTING FORMATS FOR TELEPHONE NUMBERS Use the same format for each number. Only the pager format can be used with other reporting formats. For more information, refer to Automatic Report Code Programming on page 41. Digiplex DGP-NE96 - 32 - Programming Guide...
  • Page 33: System Event Call Direction

    Backup on Telephone #2 Enabled Backup on Telephone #2 Enabled Disabled Disabled Backup on Telephone #3 Disabled Enabled Backup on Telephone #3 Disabled Enabled Backup on Telephone #4 Disabled Enabled Backup on Telephone #4 Disabled Enabled Digiplex DGP-NE96 - 33 - Programming Guide...
  • Page 34: Partition Settings

    ___ ___ : ___ ___ ___ ___ : ___ ___ Schedule A ___ ___ : ___ ___ ___ ___ : ___ ___ [3803] Partition 8 Schedule B ___ ___ : ___ ___ ___ ___ : ___ ___ Digiplex DGP-NE96 - 34 - Programming Guide...
  • Page 35 Partition Timers Description Partition 1 Partition 2 Partition 3 Partition 4 Partition 5 Partition 6 Partition 7 Partition 8 Section Data Section Data Section Data Section Data Section Data Section Data Section Data Section Data Decimal Values from 000 to 255 Arming/Disarming Schedule Tolerance [3104] __/__/__...
  • Page 36 SECTION [3421] : Partition 4 SECTION [3521] : Partition 5 SECTION [3621] : Partition 6 Option = Default Setting) Option = Default Setting) Option = Default Setting) Disabled Enabled Disabled Enabled Disabled Enabled Arm/Disarm with Partition 1 Arm/Disarm with Partition 1 Arm/Disarm with Partition 1 Arm/Disarm with Partition 2 Arm/Disarm with Partition 2...
  • Page 37 Partition Panic Alarm Options Partition 1 Partition 2 Partition 3 Partition 4 Partition 5 Partition 6 Partition 7 Partition 8 [3123] [3223] [3323] [3423] [3523] [3623] [3723] [3823] Option = Default Setting) Panic 1 (Keys 1 & 3) Panic 2 (Keys 4 & 6) Panic 3 (Keys 7 &...
  • Page 38 Partition Arming / Disarming Event Call Direction Partition 1 Partition 2 Partition 3 Partition 4 Partition 5 Partition 6 Partition 7 Partition 8 [3127] [3227] [3327] [3427] [3527] [3627] [3727] [3827] Option = Default Setting) Call Telephone Number 1 Call Telephone Number 2 Call Telephone Number 3 Call Telephone Number 4 Backup on Telephone Number 1...
  • Page 39: Special And Trouble Report Codes

    (refer to “Disarming Report Schedules” on page 34) [3928] __/__ Remote Disarming (APR3-ADM2) [3961] __/__ Wireless Transmitter Supervision Trouble [3929] Future Use [3962] Future Use [3963] Future Use [3964] Future Use [3965] __/__ Phone Number 1 Fail to Communicate Digiplex DGP-NE96 - 39 - Programming Guide...
  • Page 40: Other Settings And Modes

    Paradox Memory Card (PMC-3) [4010] Download from the Memory Key to the control panel except sections [0001] to [0096] and [0501] to [0532].
  • Page 41 Keyswitch arming/disarming report codes (sections from [0701] to [0832]) to default values. [4048] Entering this section will clear all user labels, door labels, partition labels, and zone labels from sections [0301] to [0396]. Digiplex DGP-NE96 - 41 - Programming Guide...
  • Page 42 1 12A - Panic alarm PA - Panic Alarm Panic 2 - Medical 1 1AA - Medical alarm MA - Medical Alarm Panic 3 - Fire 1 115 - Pull Station FA - Fire Alarm Digiplex DGP-NE96 - 42 - Programming Guide...
  • Page 43 1 627 - Program mode Entry LB - Local Program Installer programming finished 1 628 - Program mode Exit LS - Local Program Success WinLoad Login request 1 411 - Call Back Request RB - Remote Program Begin Digiplex DGP-NE96 - 43 - Programming Guide...
  • Page 44 Low Water Level REMOTE ACCESS - 410 Pump Activated Callback Request Made Pump Failure Success - Download Access SYSTEM TROUBLES - 300 & 310 Unsuccessful Access System Trouble System Shutdown AC Loss Dialer Shutdown Digiplex DGP-NE96 - 44 - Programming Guide...
  • Page 45: Control Panel Hardware Connections

    Control Panel Hardware Connections Single Zone Inputs ATZ - Double Zone Inputs Digiplex DGP-NE96 - 45 - Programming Guide...
  • Page 46 (G) 80PU = 270PU<454PU = OK As indicated in Table 2 on page 48, this run of wire can support 136PU. Total PU on this run of wire: (A) 40PU + (C) 30PU = 70PU<136PU = OK Digiplex DGP-NE96 - 46 - Programming Guide...
  • Page 47 For TBR-21 compliance, please note the following: The DGP-NE96 can be connected to the telephone network via an RJ-11 connector. The Maximum Dialing Attempts cannot exceed 15 attempts (section [3056] on page 32). Digiplex DGP-NE96 - 47 - Programming Guide...
  • Page 48 STEP 3: Due to the degradation of a power signal over long distances (if this were the case, we recommend connecting a Paradox Power Supply Module, DGP2-PS17), EACH length or run of wire in the system can support only a specific number of power units (PU). Using Table 2, determine how many power units each length of wire can support.
  • Page 49 The module scan is complete when the LCD keypad begins to show the Refer to the UL and ULC Warnings section of the Digiplex DGP-NE96 Reference & partition status. Only after the module scan is complete will the control panel be fully operational.
  • Page 50 Built-in RTC Digiplex DGP-NE96 incorporates an RTC directly on the PC board. The RTC will save the control panel’s internal clock when both the AC and battery power have been lost. After power is lost and then restored, the control panel will verify with and then retrieve the time from the RTC. The control panel will verify and compare its time with the time stored in the RTC every hour.
  • Page 51 __________________________________________________________________________________ __________________________________________________________________________________ __________________________________________________________________________________ __________________________________________________________________________________ __________________________________________________________________________________ __________________________________________________________________________________ __________________________________________________________________________________ __________________________________________________________________________________ __________________________________________________________________________________ __________________________________________________________________________________ __________________________________________________________________________________ __________________________________________________________________________________ __________________________________________________________________________________ __________________________________________________________________________________ __________________________________________________________________________________ __________________________________________________________________________________ __________________________________________________________________________________ __________________________________________________________________________________ __________________________________________________________________________________ __________________________________________________________________________________ __________________________________________________________________________________ __________________________________________________________________________________ __________________________________________________________________________________ __________________________________________________________________________________ __________________________________________________________________________________ __________________________________________________________________________________ __________________________________________________________________________________ __________________________________________________________________________________ __________________________________________________________________________________ __________________________________________________________________________________ __________________________________________________________________________________ __________________________________________________________________________________ __________________________________________________________________________________ Digiplex DGP-NE96 - 51 - Programming Guide...
  • Page 52: Trouble Display

    For technical support in Canada or the U.S., call 1-800-791-1919 for English or 1-866-912-0600 for French, Monday to Friday from 8:00 a.m. to 8:00 p.m. EST. For technical support outside Canada and the U.S., call 00-1-450-491-7444, Monday to Friday from 8:00 a.m. to 8:00 p.m. EST. Please feel free to visit our website at www.paradox.ca. 780 Industriel Blvd., Saint-Eustache (Quebec) J7R 5V3 CANADA Tel.: (450) 491-7444...