7 Execution Log Functions
7-1-2

How to Use the Execution Log

Use the Execution Logs according to the following procedure.
STEP1
Set Execution Log.
STEP2
Insert the SD Memory Card
into the CPU Unit.
STEP3
Start the OPC UA Server.
STEP4
Check the Execution Logs.
7-1-3

Setting the Execution Log

Set the following settings in OPC UA Server Settings from Configurations and Setup - OPC UA Set-
tings in Multiview Explorer of the Sysmac Studio.
Setting
Execution Log
Number of files
Number of records
7-1-4

Checking the Execution Log

Refer to 7-2 Checking the Execution Log on page 7-13 to check Execution Logs.
7 - 4
Step
7-1-3 Setting the Execution Log on page 7-4
NJ-series CPU Unit Hardware User's Manual (Cat No.
W500)
4-1 Starting or Stopping the OPC UA Server on page 4-2
7-2 Checking the Execution Log on page 7-13
Description
Set whether or not to record Execution Logs.
Set the maximum number of Execution Log files to be
stored in the directory.
When the maximum number of files is reached, the
oldest file is deleted and a new file is created.
Set the number of records (logs) per Execution Log
file. When the set number of records is reached, a file
with the next serial number is created and then saved.
Reference
Value
• Do not record (Default)
• Record
2 to 100
(Default: 24)
Unit: files
100 to 65,536
(Default: 12,000)
Unit: records/file
NJ-series CPU Unit OPC UA User's Manual (W588)