CHAPTER 6: ACTUAL VALUES
The G60 is provided with optional GOOSE communications capability. This feature is specified as a software
option at the time of ordering. See the Order Codes section of chapter 2 for details.
The RxGOOSE Analog values display in this menu. The RxGOOSE Analog values are received via IEC 61850 GOOSE
messages sent from other devices.

6.4.10 Sensitive directional power

ACTUAL VALUES  METERING  SENSITIVE DIRECTIONAL POWER  DIRECTIONAL POWER 1(2)
 DIRECTIONAL
 POWER 1
The effective operating quantities of the sensitive directional power elements display here. The display is useful to calibrate
the feature by compensating the angular errors of the CTs and VTs with the use of the

6.4.11 Stator ground

ACTUAL VALUES  METERING  STATOR GROUND
 STATOR GROUND
Magnitudes of the third harmonic components of the machine neutral point voltage (VN), the zero-sequence voltage at the
machine terminals (V0), and in the vector sum of the neutral point voltage and zero-sequence voltage (VN + V0) are
available for display. The values are calculated for a signal source specified under the
These readings can be useful when selecting a pickup and supervision setting for the 100% stator ground and third
harmonic neutral undervoltage protection elements.

6.4.12 Sub-harmonic stator ground

ACTUAL VALUES  METERING  SUB-HARMONIC STATOR GROUND
 SUB-HARMONIC
 STATOR GROUND
Actual values related to sub-harmonic stator ground protection display in this menu.

6.4.13 Field ground

ACTUAL VALUES  METERING  FIELD GROUND
 FIELD
 GROUND
G60 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
DIRECTIONAL POWER 1
3Φ: 0.000 W
STATOR GND 3RD HARM
VN: 0.000 V
STATOR GND 3RD HARM
VN+V0: 0.000 V
STATOR GND 3RD HARM
V0: 0.000 V
SH INJECTION VOLTS
0.000 V
SH INJECTION AMPS
0.000 A
SH CURRENT ANGLE
STATOR GND. RESIST:
> 500.000 kΩ
FIELD GROUND RESIST
500 kΩ
METERING
and
settings.
RCA
CALIBRATION
settings menu.
STATOR GROUND
6
6-25