Direct Inputs And Outputs - GE G60 Instruction Manual

Generator protection system
Hide thumbs Also See for G60:
Table of Contents

Advertisement

INPUTS/OUTPUTS
To acknowledge/reset a specific annunciator window, use the Up, Down, Left and Right pushbuttons to select the
window, and press the RESET or ENTER pushbutton
All annunciator windows can be reset remotely by programming a Virtual Input (for example Virtual Input 1) as the
input to the
RESET ANNUNCIATOR
(or function 10h with address 400h) is used to set the state of Virtual Input 1.
For the
RESET ANNUNCIATOR
command, operand source and manual source. Each individual source of a
its individual operand
operands generates an event in the event record when activated. The setting here selects the operand that activates the
RESET ANCTR OP (OPRD)
activates the
RESET ANCTR OP (MNUL)

5.9.6 Direct inputs and outputs

5.9.6.1 Direct inputs
SETTINGS  INPUTS/OUTPUTS  DIRECT INPUTS  DIRECT INPUT 1(32)
 DIRECT INPUT 1
5
These settings specify how the direct input information is processed.
DIRECT INPUT 1 NAME
DIRECT INPUT 1 DEVICE ID
identified here.
DIRECT INPUT 1 BIT NUMBER
identified as
DIRECT INPUT 1 BIT NUMBER
DIRECT INPUT 1 DEFAULT STATE
following choices are available:
On — Defaults the input to Logic 1
Off — Defaults the input to Logic 0
Latest/On — Freezes the input in case of lost communications. When the latest state is not known, such as after relay
power-up but before the first communication exchange, the input defaults to Logic 1. When communication resumes,
the input becomes fully operational.
Latest/Off — Freezes the input in case of lost communications. When the latest state is not known, such as after relay
power-up but before the first communication exchange, the input defaults to Logic 0. When communication resumes,
the input becomes fully operational.
5.9.6.2 Direct outputs
SETTINGS  INPUTS/OUTPUTS  DIRECT OUTPUTS  DIRECT OUTPUT 1(32)
 DIRECT OUTPUT 1
5-368
setting. Then the Modbus execute function 05h with operation code 1000h command
setting, the
RESET ANCTR OP
or
RESET OP (OPRD)
RESET ANCTR OP (MNUL)
operand. The RESET pushbutton on the front panel or the reset command from the software
operand.
DIRECT INPUT 1
NAME: Dir Ip 1
DIRECT INPUT 1
DEVICE ID: 0
DIRECT INPUT 1
BIT NUMBER:
DIRECT INPUT 1
DEFAULT: Off
DIRECT INPUT 1
EVENTS: Disabled
— This setting allows the user to assign a descriptive name to the direct input.
— Represents the source of direct input 1. The specified direct input is driven by the device
— The bit number to extract the state for direct input 1. Direct Input 1 is driven by the bit
. This corresponds to the direct output number of the sending device.
— Represents the state of the direct input when the associated direct device is offline. The
DIRECT OUT 1 NAME:
Dir Out 1
FlexLogic operand is activated by the two sources of
RESET ANNUNCIATOR
to identify the source of the command. Each of these two
Range: up to 12 alphanumeric characters
Range: 0 to 16
Range: 0 to 32
0
Range: On, Off, Latest/On, Latest/Off
Range: Enabled, Disabled
Range: up to 12 alphanumeric characters
G60 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
RESET
command also activates