1) DESCRIPTION AND COMPATIBILITY
The Amana PHWT-A200 is a programmable electronic
thermostat, which can be used with the following
heating/cooling applications:
• Cooling/ Conventional PTAC Units (PTC) with or
without Electric Heat
• Heat Pump PTAC Units (PTH or HEH) with or
without Electric Heat
2) SPECIFICATIONS
• Input Voltage: 19 to 30 VAC
• Output Rating: Max. 1.5A per terminal (3A total)
• Temperature Control: 45°F to 90°F (7°C to 32°C)
• Temperature Accuracy: ± 1°F (± 0.5°C)
• Wire Terminals:
C
24 VAC Common
GL
Fan LOW Speed
GH
Fan HIGH Speed
W2
2nd Stage or Auxiliary Heating Signal
W1
1st Stage Heating Signal
Y
Cooling Signal
R
24 VAC Hot
B/O
Reversing Valve
AMANA PHWT-A200 THERMOSTAT
3) SAFETY INFORMATION
• This thermostat is for LOW voltage applications only.
• Turn OFF electricity to all heating and cooling
components.
• All wiring must conform to applicable local
and national building and electrical codes and
ordinances.
4) TO REMOVE EXISTING THERMOSTAT
1. Write down the letters printed near each wire
terminal that is used, and the color of each wire it
is connected to; self-adhesive wire labels are also
enclosed.
2. Carefully remove wires from existing thermostat
and bend so they cannot fall back into wall or
touch each other.
3. Remove existing thermostat base from the wall.
5) TO INSTALL NEW THERMOSTAT
1. Mount the thermostat on an inside wall about
five feet above the floor in an area that has good
circulation, but is not directly affected by a vent
or duct.
2. If painting or construction is still ongoing, cover
the thermostat completely or wait until work is
complete before mounting thermostat.
3. If new mounting holes are needed, mark the
placement of the new mounting holes through
the thermostat base. Using a 3/16" drill bit,
drill the holes you have marked and insert the
supplied wall anchors.
4. Feed the wires through the wire opening in the
base and use supplied screws to mount base to
the wall.
5. Using Section 7) WIRING DIAGRAMS, wire each
terminal on the new thermostat base. Ensure that
the bare end is fully seated into the connector,
then tighten securely. Pull gently on wires to
ensure they are secure.
6. Place thermostat front back onto the base.
7. Restore power back to heating and cooling
components and thermostat.
8. See Section 8) INSTALLER SETTINGS MENU, to
adjust the required settings needed for each
system type.

Advertisement

loading

Summary of Contents for Amana PHWT-A200

  • Page 1 1) DESCRIPTION AND COMPATIBILITY circulation, but is not directly affected by a vent The Amana PHWT-A200 is a programmable electronic or duct. thermostat, which can be used with the following 2.
  • Page 2: Front Panel Controls

    6) FRONT PANEL CONTROLS UP AND DOWN BUTTONS: THERMOSTAT SYSTEM MODE BUTTON: System Mode Button UP button DOWN button Press System Mode button until desired mode is UP / DOWN = used for raising or lowering the target set underlined, after 2 seconds with no button press the temperature and selecting user options and settings in underlined system mode is entered.
  • Page 3 7) WIRING DIAGRAMS UP TO 2H/1C HEAT PUMP APPLICATIONS: UP TO 1H/1C CONVENTIONAL APPLICATIONS: (AMANA PTH & HEH PTAC MODELS): (AMANA PTC PTAC MODELS) ** see note 1 HP Reversing Valve NOT USED 24V Power 24V Power Heat Pump Compressor...
  • Page 4: Installer Settings

    8) INSTALLER SETTINGS SOFTWARE CONFIGURATION SETTINGS MENU# SETTING OPTIONS NOTE: Waiting 1-Minute with no button presses will exit Scale F, C the installer settings menu with all items saved as they Zero, -5F to +5F were last shown on the display screen. Temp.
  • Page 5: Automatic Daylight Savings Time

    9) AUTOMATIC DAYLIGHT SAVINGS TIME SETTING DESCRIPTIONS: 01 (Scale): Displayed temperatures shown in F/C degrees. By default, the thermostat will automatically adjust 02 (Temp. Calibration): Gives user flexibility to adjust the clock for Daylight Savings. This can be disabled by the perceived measured temperature that is used for changing the Auto Daylight Savings (setting 16) option thermal control.
  • Page 6 12) ADJUSTING THE HEAT OR COOL 13) ENTERING EMERGENCY HEAT MODE TEMPERATURE PROGRAM (HP UNITS ONLY) • Each period ends at the start time of the next • While in regular HEAT mode, press and hold BOTH upcoming period. the Mode and Fan buttons for at least 5 seconds, NOTE: If configured to use only 2 periods, only DAY until the screen changes.