Setpoint Values For Monitoring The Bearing Temperature - Siemens SIMOTICS XP 1LA5 Compact Operating Instructions

Low-voltage motors
Hide thumbs Also See for SIMOTICS XP 1LA5:
Table of Contents

Advertisement

7
Commissioning
When carrying out any work on the machine, observe the general safety instructions
(Page 77) and the specifications contained in EN 50110-1 regarding safe operation
of electrical equipment.
7.1
Setpoint values for monitoring the bearing
temperature
Prior to commissioning
If the machine is equipped with bearing thermometers, set the temperature value for
disconnection on the monitoring equipment before the first machine run.
Table 7-1
Set values for monitoring the bearing temperatures before commis-
sioning
Set value
Alarm
Shutting down
Normal operation
Measure the normal operating temperature of the bearings T
location in °C. Set the values for shutdown and warning corresponding to the
operating temperature T
Table 7-2
Set values for monitoring the bearing temperatures
Set value
Alarm
Shutting down
Explosion-protected machines
56100000002002, 01/2016
.
op
Temperature
115 °C
120 °C
at the installation
op
Temperature
T
+ 5 K ≤ 115 °C
operation
T
+ 10 K ≤ 120 °C
operation