7.
ELECTRICAL DATA
7-3
M o d e l : 2xEDS25/GC9+9
Model
Power Supply
Max. Current
Power Supply
Indoor And Outdoor Unit Connections
Connections cable
1. If there is a additional electric-heater, the cable must be thicken one grade.
2. Use supply wire sizes as per local electrical codes and regulations.
7-4
Model:
Model
Power Supply
Max. Current
Power Supply
Indoor And Outdoor Unit Connections
Connections cable
1. If there is a additional electric-heater, the cable must thicken one grade.
2. Use supply wire sizes as per local electrical codes and regulations.
Service Manual - EDS
EDS 52+52 / GC17+17
EDS25X2+EDS35 / GC9+9+12
EDS25 2+EDS52 / GC9+9+17
EDS25+EDS35+EDS52/ GC9+12+17
EDS35X3 / GC12+12+12
Indoor Unit
Outdoor Unit
A
2
mm
2
mm
Revision
2xEDS35/GC12+12
Indoor Unit
Outdoor Unit
1N~230V-50Hz
A
2 EDS52
2 EDS25 +EDS35
GC17+17
GC9+9+12
1N~230V-50Hz
23.7
19.5
3G, 4.0
3G, 2.5
6G, 1.5
6G, 1.5
0
ELECTRICAL DATA
2 EDS25
2 EDS35
GC9+9
GC12+12
12.8
17.6
3G,1.5
3G, 2.5
6G, 1.0
6G, 1.5
2 EDS25 +EDS52 EDS25+EDS35+EDS52
GC9+9+17
GC9+12+17
24.1
27.3
3G, 4.0
3G, 4.0
6G, 1.5
6G, 1.5
3 EDS35
GC12+12+12
24.7
3G, 4.0
6G, 1.5
7-2