Page 1
Design, Installation and Maintenance instruction R410A Heat Pump 50 Hz FlowLogic II 2016...
Page 2
CONTENTS R410A Full-variation multi-combination system PART 1General Information --------------------------------------------------------03 PART 2 Indoor Units ------------------------------------------------------------------26 4-way cassette type indoor unit------------------------------------------27 Ceiling concealed type indoor unit--------------------------------------57 Med static pressure duct type indoor unit----------------------------78 High static pressure duct type indoor unit--------------------------103 Convertible type indoor unit---------------------------------------------150 Wall mounted type indoor unit------------------------------------------188 Console type indoor unit--------------------------------------------------204 PART 3 Outdoor Units---------------------------------------------------------------222...
Page 11
Allowable pipe length and height difference outdoor1 when the distance between outdoors is over 2m, the oil trap must be set (upright projecting pipe, 200mm high) outdoor2 outdoor3 below 2m below 2m over 200mm over 200mm L1 < 10m L2+L3 < 10m L7+L14+L13 <...
Page 25
1. 4-way cassette type indoor unit--------------------------------------------------27 2. Ceiling concealed type indoor unit----------------------------------------------56 3. Med static pressure duct type indoor unit------------------------------------78 4. High static pressure duct type indoor unit-----------------------------------103 5. Convertible type indoor unit-------------------------------------------------------150 6. Wall mounted type indoor unit----------------------------------------------------188 7.Console type indoor unit-------------------------------------------------------------204...
Page 26
1. Features -----------------------------------------------------------------------------------28 2. Specifications----------------------------------------------------------------------------29 3. Dimensions--------------------------------------------------------------------------------32 4. Piping diagrams--------------------------------------------------------------------------35 5. Wiring diagrams-------------------------------------------------------------------------36 6. Electric characteristics----------------------------------------------------------------37 7. Capacity tables---------------------------------------------------------------------------38 8. Air velocity and temperature distributions--------------------------------------41 9. Noise level---------------------------------------------------------------------------------45 10. Installation-------------------------------------------------------------------------------46 11.Accessories------------------------------------------------------------------------------55...
Page 40
CBV009 CBV012 CBV016 a. Cooling / Air Velocity Distribution Cooling Blowy angle:40 Air Velocity Distribution 2.7m 1.5m/s 1.5m/s 1.0m/s 1.0m/s 0.5m/s 0.5m/s b. Cooling / Temperature Distribution Cooling Blowy angle:40 Temperature Distribution 2.7m...
Page 41
c. Heating / Air Velocity Distribution Heating Blowy angle:70 Air velocity Distribution 2.7m 1.5m/s 1.5m/s 1.0m/s 1.0m/s 0.5m/s 0.5m/s d. Heating / Temperature Distribution Heating Blowy angle:70 Temperature Distribution 2.7m...
Page 42
CCV018 CCV024 CCV028 CCV030 CCV038 CCV048 a. Cooling / Air Velocity Distribution Cooling Blowy angle:40 Air Velocity Distribution 2.7m 1.5m/s 1.5m/s 1.0m/s 1.0m/s 0.5m/s 0.5m/s b. Cooling / Temperature Distribution Cooling Blowy angle:40 Temperature Distribution 2.7m...
Page 43
c. Heating / Air Velocity Distribution Heating Blowy angle:70 Air velocity Distribution 2.7m 1.5m/s 1.5m/s 1.0m/s 1.0m/s 0.5m/s 0.5m/s d. Heating / Temperature Distribution Heating Blowy angle:70 Temper ature Distribution 2.7m...
Page 68
air flow and static pressure curves DAV007 super high high static pressure (Pa) air flow and static pressure curves DAV009 super high high static pressure (Pa)
Page 69
air flow and static pressure curves DAV012 super high high static pressure (Pa) air flow and static pressure curves DAV016 1000 super high high static pressure (Pa)
Page 70
air flow and static pressure curves DAV018 1400 1350 1300 super high 1250 high 1200 1150 1100 1050 1000 static pressure (Pa) air flow and static pressure curves DAV024 1400 1350 1300 super high 1250 high 1200 1150 1100 1050 1000 static pressure (Pa)
Page 88
air flow and static pressure curves DBV018 1400 1300 1200 super high high 1100 1000 static pressure(Pa) air flow and static pressure curves DBV024 1400 1300 1200 super high high 1100 1000 static pressure(Pa)
Page 89
air flow and static pressure curves DBV028 1700 1600 1500 super high high 1400 1300 1200 1100 static pressure(Pa) air flow and static pressure curves DBV030 2300 2200 2100 super high high 2000 1900 1800 1700 static pressure(Pa)
Page 90
air flow and static pressure curves DBV038 2300 2200 2100 super high high 2000 1900 1800 1700 static pressure(Pa) air flow and static pressure curves DBV048 2300 2200 2100 super high high 2000 1900 1800 1700 static pressure(Pa)
Page 115
air flow and static pressure curves DCV018 1400 1200 1000 super high high static pressure (Pa) air flow and static pressure curves DCV024 1400 1200 1000 super high high static pressure (Pa)
Page 116
air flow and static pressure curves DCV028 1400 1200 1000 super high high static pressure (Pa) air flow and static pressure curves DCV030 2000 1800 1600 super high high 1400 1200 1000 static pressure (Pa)
Page 117
air flow and static pressure curves DCV038 2000 1800 1600 super high high 1400 1200 1000 static pressure (Pa) air flow and static pressure curves DCV048 2500 2300 2100 super high high 1900 1700 1500 1300 static pressure (Pa)
Page 118
DCV072~ 96 1. The number in the circle stands for the step on the fan speed controller. 2. The red line shows the air flow and the static pressure varies due to the different steps in high speed. The blue dashed line shows the air flow and the static pressure varies due to the different steps in low speed.
Page 140
a) On the floor a. Cooling / Air Velocity Distribution Cooling Blowy angle:25 Air Velocity Distribution 2.4m 0.5m/s 1.0m/s 1.5m/s 5.5m b. Cooling / Temperature Distribution Cooling Blowy angle:25 Temperature Distribution 2.4m 5.5m...
Page 141
c. Heating / Air Velocity Distribution Heating Blowy angle:5 Air velocity Distribution 2.4m 0.5m/s 1.0m/s 1.5m/s 5.5m d. Heating / Temperature Distribution Heating Blowy angle:5 Temperature Distribution 2.4m 5.5m...
Page 142
b) Ceiling a. Cooling / Air Velocity Distribution Cooling Blowy angle:25 Air Velocity Distribution 2.4m 1.5m/s 1.0m/s 0.5m/s 5.5m b. Cooling / Temperature Distribution Cooling Blowy angle:25 Temperature Distribution 2.4m 5.5m...
Page 143
c. Heating / Air Velocity Distribution Heating Blowy angle:65 Air velocity Distribution 2.4m 1.5m/s 1.0m/s 0.5m/s 5.5m d. Heating / Temperature Distribution Heating Blowy angle:65 Temperature Distribution 2.4m 5.5m...
Page 167
HAV007 HAV009 HAV012 HAV016 HAV018 HAV024 EEV inside put The EEV box inside put, easy for installation High-quality DC fan motor, reduce the indoor unit noise greatly New fashion design...
Page 191
0| 3JR VFLODJTY BNE TFMPFRBTURF EJSTRJCUTJON a. Cooling / Air Velocity Distribution Cooling Blowy angle:25 Air Velocity Distribution 2.4m 0.4m/s 0.8m/s 1.2m/s 5.5m b. Cooling / Temperature Distribution Cooling Blowy angle:25 Temperature Distribution 2.4m 5.5m...
Page 192
c. Heating / Air Velocity Distribution Heating Blowy angle:5 Air velocity Distribution 0.4m/s 0.8m/s 1.2m/s d. Heating / Temperature Distribution Heating Blowy angle:5 Temperature Distribution...
Page 248
7 . Capacity calculation due to capacity modification coefficient...
Page 250
(2) Calculation method of heating capacity---Heating capacity to be known = Heating capacityx (A x B x C x D x E x F) W B. Capacity modification value under outdoor air wet-bulb C. Capacity modification value A. Capacity modification value temperature condition under airflow variation rate of under indoor air dry-bulb...
Page 259
a. Allowable pipe length and height difference Single way total pipe length 300m Single way max. pipe length Max. 150m Main pipe between outdoor to 1 branch Max. 90m Pipe length between outdoors Less than 10m to 1 branch pipe Height difference between indoor and Outdoor is upper Max.
Page 260
outdoor1 outdoor 2 outdoor 3 outdoor1 outdoor3 outdoor2 Installation at high difference: outdoor1 outdoor2 outdoor3...
Page 261
outdoor3 outdoor2 outdoor1 Oil trap (upright projecting pipe, 200mm high), as the figure: outdoor2 outdoor3 outdoor1 Below is forbidden (compressor oil will flow into the lowest outdoor). outdoor3 outdoor2 outdoor1...
Page 262
c. Allowable pipe length and height difference outdoor1 when the distance between outdoors is over 2m, the oil trap must be set (upright projecting pipe, 200mm high) outdoor2 outdoor3 below 2m below 2m over 200mm over 200mm L1 < 10m L2+L3 <...
Page 263
2.3 Pipe specification: outdoor gather pipe the first branch a. Pipe “a” diameter (between indoor and branch pipe) (depends on indoor pipe, for wall mounted unit, please refer to its specification) Indoor(*100W) Gas pipe Liquid pipe φ9.52( : φ12.7) φ6.35 22~28 φ12.7(...
Page 272
(1) Outdoor pipe dimension 18~32HP 34~48HP Liquid pipe Liquid pipe Gas pipe Gas pipe The pipe “a, b, c, d” should be confirmed as to the below table. Former outdoor capacity Liquid pipe (a, c) Gas pipe (b, d) φ15.88 φ28.58 ~62.0KW φ15.88...
Page 350
Wired controller functions RWV01 1. Brief Functions 1.1 Being connected with indoor through 3 wires, and can control 16 groups of indoor. 1.2 Can combine with another wired controller, the slave one will be in the same step with the master one. 1.3 Set unit number for indoor unit in one group 1.4 Record the last twice failures of each indoor in one group 1.5 1 port is A/D input (room temperature sensor), 16 ports are function input, 12 ports is...
Page 351
controller, so the display will be different. Master/Slave either Only can be Master controller selection Master Slave controller 5. LCD display The LCD appearance and the display icons: MODE SWING TEMP HEALTH T I M E CLOCK TIMER RECOVERY F I L T E R CHECK RESET O N / O F F...
Page 352
1. ON/OFF button Press “ON/OFF” to change over the state ON/OFF; In running, LED is on; in stop state, LED is off. In switchover state of cooling or heating, press ON/OFF for 5 seconds to enter compulsory running mode. 2. MODE button 2.1 The mode of 1# indoor will decide the mode which wired controller can display and set.
Page 353
clock. When selecting TIMER OFF, adjust the clock of TIMER OFF, TIMER OFF will flash at 1Hz, press +/- to adjust the clock. When selecting TIMER ON/OFF, adjust the clock of TIMER ON/OFF, display TIMER ON/OFF at the same time, firstly TIMER ON will flash at 1Hz and TIMER OFF is on, which shows to set the clock of TIMER ON, then TIMER OFF will flash at 1Hz and TIMER ON is on to set the clock of TIMER OFF.
Page 354
2.13 RESET button RESET is equal that the controller is restarted up. 7. Icon display 7.1 [CENTRAL] After receiving the central control signal from indoor, the controller displays [CENTRAL], or [CENTRAL] is off. Central control mode: normal on. Compulsory mode: flash (1Hz) 7.2 [OPERATION] After the controller starts up, when compressor is running, the controller will display [OPERATION];...
Page 355
In the state of power on or power off, press [CHECK] button, enter the malfunction-querying mode of all indoor units in the group. Then [CHECK] and [UNIT NO.] will display, and the actual indoor numbers will be displayed in some sequence (unit number is in decimals). At the same time, in the time region, there will be the current malfunction and the latest time malfunction, the displaying format is [XX YY], in which XX stands for the current malfunction, if normal, it will display “――”;...
Page 356
original. 3) In compulsory operation, only “ON/OFF”, “TEMP +”, “TEMP –“ can be set. 4) Only “ON/OFF” can cancel this control. 5) The indoor units in one group will enter or quit the trial operation at the same time. 8.9 Filter elevating function: (only for the unit with elevating function) In power off state, press [HEALTH] for 10 seconds to enter filter elevating set state.