YBZ214-318-430 Indoor Units Outdoor Units AWSI-HZD009-H11 AWSI-HYD009-H11 AWAU-YBZ214-H11 AWSI-HZD012-H11 AWSI-HYD012-H11 AWAU-YBZ318-H11 AWSI-HZD018-H11 AWSI-HYD018-H11 AWAU-YBZ430-H11 REFRIGERANT R410A HEAT PUMP JUNE- 2011 SM YBZ H11 1-A.1 GB Version:2...
Page 2
LIST OF EFFECTIVE PAGES LIST OF EFFECTIVE PAGES Note: Changes in the pages are indicated by “Revision #” in the footer of each effected page (when none indicates any changes in the relevant page). All pages in the following list represent effected/ non effected pages divided by chapters.
INTRODUCTION INTRODUCTION General The YBZ DC inverter multisplits outdoor is a multi-tubing system with 2, 3 or 4 connected indoor units. The multi-split inverter is a high level technology product for residential and commercial application offering comfort, low noise operation and energy saves.
INTRODUCTION Indoor Unit The indoor unit is wall mounted, and can be easily fitted to many types of residential locations. It includes: • LED display • Variable speed with PG motor • Motorized flap • High efficiency filtration to ensure a best Air Quality: Advanced filtering combine mechanical, Photo-catalytic + Bi-anti bacterial and observe bad gaseous and smokes.
INTRODUCTION Outdoor Unit The outdoor units can be installed as floor or wall mounted units by using a wall supporting bracket. The metal sheets are protected by anti- corrosion paint work allowing long life resistance. All outdoor units are pre-charged. For further information please refer to the Product Data Sheet, Chapter 2.
PRODUCT DATASHEET PRODUCT DATA SHEET Model Outdoor Unit YBZ214 Installation Method of Pipe Flared Characteristics Units Cooling Heating Capacity (4) 3.90(2.00-4.70) 4.30(2.50-5.50) Power input (4) 1.14(0.50-2.00) 1.13(0.58-2.15) EER (Cooling) or COP(Heating) (4) 3.42 3.80 Energy efficiency class 220-240 Power supply Rated current 5.11 5.06...
Page 10
PRODUCT DATA SHEET Model Outdoor Unit YBZ318 Installation Method of Pipe Flared Characteristics Units Cooling Heating Capacity (4) 6.80(2.20-10.00) 8.00(2.80-11.00) Power input (4) 2.11(0.65-4.50) 2.21(0.98-3.95) EER (Cooling) or COP(Heating) (4) 3.22 3.62 Energy efficiency class 220-240 Power supply Rated current 9.45 9.90 0.97...
Page 11
PRODUCT DATASHEET Model Outdoor Unit YBZ318 Installation Method of Pipe Flared Characteristics Units Cooling Heating Capacity (4) 7.80(2.20-10.00) 8.70(2.80-11.00) Power input (4) 2.42(0.65-4.50) 2.40(0.98-3.95) EER (Cooling) or COP(Heating) (4) 3.22 3.63 Energy efficiency class 220-240 Power supply Rated current 10.8 10.7 Power factor 0.97...
Page 12
PRODUCT DATA SHEET Model Indoor Unit HZD/HYD009 Installation Method of Pipe Flared Characteristics Units Cooling Heating Capacity (4) 2.60 2.80 220-240 Power supply Fan type & quantity Crossflow x 1 Cooling SH/H/M/L 1300/1100/900/700 Fan speeds Heating SH/H/M/L 1300/1140/980/820 Air flow (1) SH/H/M/L m3/hr 600/500/350/280...
PRODUCT DATASHEET Model Indoor Unit HZD/HYD018 Installation Method of Pipe Flared Characteristics Units Cooling Heating Capacity (4) 5.30 5.80 220-240 Power supply Fan type & quantity Crossflow x 1 Cooling SH/H/M/L 1300/1100/950/800 Fan speeds Heating SH/H/M/L 1400/1200/1050/900 Air flow (1) SH/H/M/L m3/hr 800/680/560/460...
RATING CONDITIONS RATING CONDITIONS Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units). Cooling: Indoor: C DB 19 C WB Outdoor: 35 C DB Heating: Indoor: C DB Outdoor: 7 C DB 6 C WB Operating Limits R410A Indoor Outdoor...
PERFORMANCE DATA PERFORMANCE DATA YBZ214 5.1.1 Cooling Capacity (kW) ID COIL ENTERING AIR DB/WB TEMPERATURE [C OD COIL ENTERING AIR DB TEMPERATURE [C DATA 22/15 24/17 27/19 29/21 32/23 80 - 110 % of nominal -10 - 20 80 - 105 % of nominal (protection range) 25 - 50 % of nominal 4.18...
Page 20
PERFROMANCE DATA 5.1.3 Heating Capacity (kW) ID COIL ENTERING AIR DB TEMPERATURE [C OD COIL ENTERING AIR DB/WB TEMPERATURE DATA 2.29 2.15 2.01 -15/-16 0.72 0.83 0.93 2.74 2.60 2.46 -10/-12 0.83 0.94 1.04 3.08 2.94 2.80 -7/-8 0.92 1.02 1.12 3.26 3.11...
Page 21
PERFORMANCE DATA YBZ318 5.2.1 Cooling Capacity (kW) ID COIL ENTERING AIR DB/WB TEMPERATURE [C OD COIL ENTERING AIR DB TEMPERATURE [C DATA 22/15 24/17 27/19 29/21 32/23 80 - 110 % of nominal -10 - 20 80 - 105 % of nominal (protection range) 25 - 50 % of nominal 7.30...
Page 22
PERFROMANCE DATA 5.2.3 Heating Capacity (kW) ID COIL ENTERING AIR DB TEMPERATURE [C OD COIL ENTERING AIR DB/WB TEMPERATURE DATA 4.26 4.00 3.73 -15/-16 1.41 1.62 1.82 5.11 4.84 4.58 -10/-12 1.63 1.83 2.04 5.74 5.48 5.21 -7/-8 1.79 1.99 2.20 6.06 5.79...
Page 23
PERFORMANCE DATA YBZ430 5.3.1 Cooling Capacity (kW) ID COIL ENTERING AIR DB/WB TEMPERATURE [C OD COIL ENTERING AIR DB DATA 22/15 24/17 27/19 29/21 32/23 TEMPERATURE [C 80 - 110 % of nominal -10 - 20 80 - 105 % of nominal (protection range) 25 - 50 % of nominal 8.37...
Page 24
PERFROMANCE DATA 5.3.3 Heating Capacity (kW) ID COIL ENTERING AIR DB TEMPERATURE [C OD COIL ENTERING AIR DB/WB TEMPERATURE DATA 4.63 4.35 4.06 -15/-16 1.54 1.76 1.98 5.55 5.27 4.98 -10/-12 1.77 1.99 2.21 6.24 5.95 5.67 -7/-8 1.94 2.17 2.39 6.59 6.30...
ELECTRICAL DATA ELECTRICAL DATA MODEL YBZ214 YBZ318 YBZ430 To outdoor Power Supply 1PH-220-240V-50Hz Max Current, A Circuit Breaker, A Power Supply Wiring No. X Cross Section 3x2.5 mm 3x4.0mm 3x4.0mm Interconnecting Cable Model No. X Cross 4x1.0 mm 4x1.0 mm 4x1.0 mm Section mm NOTE...
CONTROL SYSTEM CONTROL SYSTEM 12.1 Electronic Control 12.1.1 Abbreviations Abbreviation Definition Air Condition Building Management System System Power Compressor Top Temperature sensor DC Inverter Electronic Expansion Valve Heating Element Human Machine Interface Heat Sink Temperature sensor Hertz (1/sec) – electrical frequency Indoor Coil Temperature (RT2) sensor Indoor Unit Micro Controller Unit...
Page 42
CONTROL SYSTEM 12.1.2 Compressor Frequency Control 12.1.2.1 Compressor frequency setting The Load calculation is done by each indoor unit controller, based on a PI control scheme which is based on the difference between SPT and RAT. ODU controller will decide the compressor frequency based on the total load from all the indoors. Compressor frequency will be limited within following ranges: Maximum Frequency (MaxFreq) * Minimum Frequency (MinFreq)
Page 43
CONTROL SYSTEM 12.1.3 Indoor Fan Control 8 Indoor fan speeds are determined for each model. 4 speeds for COOL modes and 4 speeds for HEAT mode. Unit Model Mode Turbo(Super high) High Medium Cooling 1300 1100 Heating 1300 1140 Cooling 1350 1150 Heating...
CONTROL SYSTEM 12.1.5.2 EEV initial value determination The EEV initial value (open loop) is determined according to the number of the active indoor units, mode, and the capacity code of the unit. 12.1.5.3 Balance time During the balance after SB the correction is not calculated. After that the correction value is updated every 5 seconds.
CONTROL SYSTEM 12.3.2.2 Partial indoors to inactive Recalculate the load immediately, for Inactive indoors, EEV opening is set to 0 step. 12.3.3 RV is OFF in Cool Mode. 12.3.4 OFAN control during Cool Mode OFAN will start 5sec before compressor start. After starting, it will run at High speed for 3 mins, and then switch to the requested speed.
Page 46
CONTROL SYSTEM 12.4.2.1 All indoors to inactive Compressor stops immediately, OFAN stops after 1 min. 12.4.2.2 Partial indoors to inactive Recalculate the load immediately, for Inactive indoors, EEV opening will follow 12.1.5.5. 12.4.3 OFAN control during Heat Mode OFAN will start 5sec before compressor starts. After starting, it will run at High speed for 40 sec then switch to the requested speed.
CONTROL SYSTEM 12.5 8 Degree Heat Mode Under heat mode, press “Save” button, the system will enter into 8 Degree Heat Mode. 1. 8 Degree Heat Mode can not exist together with Sleep mode. If Sleep Mode is selected, 8 degree Heat Mode will be canceled.
Page 48
CONTROL SYSTEM 12.8.1 Mode confliction When there are different mode settings among active indoors: a. First request priority: The first IDU which requests different mode than STBY mode will set the new operation mode. Mode confliction will be decided comparing with other IDUs’ modes. Cool (Dry) mode is conflict to Heat mode.
Page 49
CONTROL SYSTEM 12.8.4 Compressor over Heating Protection The Discharging temperature is used as the compressor’s internal temperature. If the discharge temperature rises above a certain level, the operating frequency upper limit is set to keep this temperature from going up further. Compressor frequency will be reduced when CTT reaches above 97C Compressor will stop when CTT reaches 110C If the unit stops as such protection for 6 times...
Page 50
CONTROL SYSTEM Deicing interval time is changed as a function of deicing time. If deicing time is shorter than former deicing time, the deicing interval time will be increased. If deicing time is longer than former deicing time, the deicing interval time will be decreased. 12.8.6.2 Deicing Protection Procedure When starting deicing from Heat Mode, system will work as following: 1).
Page 51
CONTROL SYSTEM compressor has run for 7min), it can not resume running automatically and display malfunction, it can resume by power reset. 12.8.11 Compressor overload protection If the compressor OLP is opened, the system will stop as protection If the OLP is resumed and compressor has stopped for 3min, the unit will be allowed to operate.
Page 52
CONTROL SYSTEM the mode is STBY. When the unit is turned on remotely, the RUN LED goes out while the current setting running mode is displayed COOL INDICATOR 1. Lights up during specified operation mode (COOL/DRY/HEAT). DRY INDICATOR HEAT INDICATOR 2* 7 segments display In normal situation, the setting temperature is displayed.
Page 53
CONTROL SYSTEM 12.10.1 Installation Test Installation test is to check any mistake in communication wiring or EEV wiring connections. Start Installation Test: RC setting: SPT=30, Cool Mode and press the button “-, +,-, +,-, +” continuously in 3 sec. Unit operation during Installation test: Unit will operate in cool mode (IFAN will stop), IDU will display “dd”.
TROUBLESHOOTING TROUBLESHOOTING 13.1 ELECTRICAL & CONTROL TROUBLESHOOTING 13.1.1 Precautions before Performing Inspection or Repair Be cautious during installation and maintenance. Do operation following the regulations to avoid electric shock and casualty or even death due to drop from high attitude. * Static maintenance is the maintenance during de-energization of the air conditioner.
TROUBLESHOOTING 13.1.3 Fault Code display from ODU The ODU will show the active fault code by its LED1, LED2, LED3 and LED4. When more than one active fault codes exist, each fault code will display in 5s interval. □ – LED OFF, ■ – LED ON, ☆ – LED Blinking Fault code LED1 LED2...
TROUBLESHOOTING 13.1.4 Fault Code display from IDU If the malfunction still exists 4min later after stop of unit due to compressor protection, error code will be directly displayed though indoor display. In other situations, fault code can be displayed by pressing LIGHT button 6 times within 4s.
TROUBLESHOOTING PFC module assembly problem. Poor heat exchange of Heatsink PFC protection PFC reactor problem. Abnormal power voltage PFC circuit problem on PCB Abnormal power input voltage. Compressor wiring mistake. Liquid and gas valve are not open. Desynchronizing of compressor EEV damaged or not proper working Poor heat exchange.
Page 59
TROUBLESHOOTING 13.2.2 Checking Power Input. If Indoor unit power LED is unlighted, power down the system and check the fuse of the Indoor unit. If the fuse is OK replace the Indoor unit controller. If the fuse has blown, replace the fuse and power up again.
EXPLODED VIEW & SPARE PART LIST EXPLODED VIEW & SPARE PART LIST 15.1 Exploded view of indoor unit: HYD009-012, HZD009-012 Service Manual – YBZ DCI 1-A.1 GB 15-1...
Page 63
EXPLODED VIEW & SPARE PART LIST 15.2 Spare part list of indoor Unit: HYD009 Part Code Part Description 02122033 Decorative Strip 2001237604_K46462 Front Panel Assy 1112208201 Filter Sub-Assy 24252019 Screw Cap 2001237501_K46462 Front Case Assy 10512119 Guide Louver 1054202001 Shaft of guide louver 10512160 Air Louver 26112486...
Page 64
EXPLODED VIEW & SPARE PART LIST 15.3 Spare part list of indoor Unit: HYD012 Part Code Part Description 02122033 Decorative Strip 2001237604_K46462 Front Panel Assy 1112208201 Filter Sub-Assy 24252019 Screw Cap 2001237501_K46462 Front Case Assy 10512119 Guide Louver 1054202001 Shaft of guide louver 10512160 Air Louver 26112486...
Page 65
EXPLODED VIEW & SPARE PART LIST 15.4 Spare part list of indoor Unit: HZD009 Part Code Part Description 20192439 Decorative Strip 20012823 Front Panel Assy 1112208201 Filter Sub-Assy 24252019 Screw Cap 20012824 Front Case Assy 10512119 Guide Louver 1054202001 Shaft of guide louver 10512160 Air Louver 26112486...
Page 66
EXPLODED VIEW & SPARE PART LIST 15.5 Spare part list of indoor Unit: HZD012 Part Code Part Description 20192439 Decorative Strip 20012823 Front Panel Assy 1112208201 Filter Sub-Assy 24252019 Screw Cap 20012824 Front Case Assy 10512119 Guide Louver 1054202001 Shaft of guide louver 10512160 Air Louver 26112486...
Page 67
EXPLODED VIEW & SPARE PART LIST 15.6 Exploded view of indoor unit: HYD018, HZD018 15-6 Service Manual – YBZ DCI 1-A.1 GB...
Page 68
EXPLODED VIEW & SPARE PART LIST 15.7 Spare part list of indoor Unit: HYD018 Part Code Part Description 20012663 Front Case 20012496_K46462 Front Panel Assy 11122104 Filter Sub-Assy 242520041 Screw Cover 20012497_K46462 Front Case Assy 10512140 Guide Louver 10542008 Axial Bush (guide louver) 10512160 Air Louver 26112232...
Page 69
EXPLODED VIEW & SPARE PART LIST 15.8 Spare part list of indoor Unit: HZD018 Part Code Part Description none Decorative Strip 20012872_K46462 Front Panel Assy 11122104 Filter Sub-Assy 242520041 Screw Cover 20012873 Front Case Assy 10512140 Guide Louver 10542008 Axial Bush (guide louver) 10512160 Air Louver 26112232...
Page 70
EXPLODED VIEW & SPARE PART LIST 15.9 Exploded view of outdoor unit: YBZ214 Service Manual – YBZ DCI 1-A.1 GB 15-9...
Page 71
EXPLODED VIEW & SPARE PART LIST 15.10 Spare part list of outdoor Unit: YBZ214 Part Code Part Description 22413015 Front Grill 01433034P Cabinet 01205161P Chassis Sub-assy 26113009 Drainage Joint 76710236 Compressor Gasket 00103501 Compressor And Fittings C-6RZ146H1A 4300040033 4-way Valve Fittings 03123438 4-way Valve Assy 3900007301 Temperature Sensor...
Page 72
EXPLODED VIEW & SPARE PART LIST 15.11 Exploded view of outdoor unit: YBZ318 Service Manual – YBZ DCI 1-A.1 GB 15-11...
Page 73
EXPLODED VIEW & SPARE PART LIST 15.12 Spare part list of outdoor Unit: YBZ318 Part Code Part Description 22415002 Front grill 01535008P Front Panel 06813401 Choke Plug 01203942P Chassis Sub-assy 06123401 Drainage Connecter 00105036 Compressor and fittings 76710207 Rubber Grommet 07225017 Gas-liquid Separator Assy 03723455...
Page 74
EXPLODED VIEW & SPARE PART LIST 15.13 Exploded view of outdoor unit: YBZ430 Service Manual – YBZ DCI 1-A.1 GB 15-13...
Page 75
EXPLODED VIEW & SPARE PART LIST 15.14 Spare part list of outdoor Unit: YBZ430 Part Code Part Description 22415002 Front grill 01535008P Front Panel 06813401 Choke Plug 01203942P Chassis Sub-assy 06123401 Drainage Connecter 00105036 Compressor and fittings 76710207 Rubber Grommet 07225017 Gas-liquid Separator Assy 03723455...
Page 76
EXPLODED VIEW & SPARE PART LIST APPENDIX Service Manual – YBZ DCI 1-A.1 GB 15-15...